Fig. 17 Parallel installation in a corner with wall shield
Combustible wall
Wall shield
•Must be 1” off the wall and 1” off the floor.
•With single wall pipe, the shield must be 49” high measured off the floor.
•With double wall pipe, the shield must be 37” high measured off the floor.
•Both shields MUST extend and join in the corner.
The wall shield must extend a minimum of 4” (102 mm) past the side of the stove
The wall shield must extend a minimum of 7” (178mm) past the ash lip of the stove
Fig. 18 Corner installation with wall shield
Wall shield
•Must be 1” off the wall and 1” off the floor.
•With single wall pipe, the shield must be 49”.
•With the double wall pipe, the shield must be 37” high.
•Both shields MUST extend and join in the corner.
Combustible wall
The wall shield must extend a minimum of 7” (178mm) past the front corner of the stove.
The wall shield must extend a minimum of 7” (178mm) past the front corner of the stove.
Fig. 19
A
B
A:Lift to open
B:Left - closed, Right - open
(Measurements in cm - for Canada)
24