LookatthetopofthewaterheaterThecoldwaterinlet.is

marked "COLD". Put two or three turns of teflon tape around the threaded end of the threaded-to-sweat coupling and around both ends of the 3/4" NPT threaded nipple. Using

flexible connectors, connect the cold water pipe to the cold water inlet of the water heater.

NOTE: This water heater is super insulated to minimize heat loss from the tank. Further reduction in heat loss

can be accomplished by insulating the hot water lines from the water heater.

INSTALLATIONCOMPLETED USING

INSTALLATION KIT

 

FLEXIBLE

 

 

WATER

 

HOT

CONNECTORS

 

 

 

e/A ITR--

 

COLe WATER

OUTLE

_'_

INLET

N t

COUPLING _

COUPLING

DRAFT HGOD

TEr_IPERATURE -

_'-_-PRESSURE

RELIEF VALVE

DISCHARGE PIPE

(Do }lot c_p or plug)

%.

AIR

GAP

FLOORDRAIN

FIGURE15.

Temperature-Pressure Relief Valve

 

 

 

Explosion Hazard

 

 

 

 

Temperature-pressure relief valve

!

 

must comply with ANSI Z21.22

• ,L_

 

,

and ASME

code•

 

 

 

 

 

 

 

 

 

 

Properly

sized

temperature-

 

 

 

pressure relief valve must be

 

 

 

installed in opening

provided.

 

 

 

 

Can result in overheating

and

 

 

 

excessive

tank pressure.

 

Can cause serious injury or death.

This heater is provided with a properly certified combination temperature - pressure relief valve by the manufacturer.

The valve is certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves and Automatic Gas Shut-off Devices for Hot Water

Supply Systems, ANSI Z21.22 and the code requirements of ASME.

If replaced, the valve must meet the requirements of local codes, but not less than a combination temperature and pressure relief valve certified as indicated in the above paragraph.

The valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 psi = 1,035kPa) and a discharge capacity not less than the water heater input rate as shown on the model rating plate.

For safe operation of the water heater, the relief valve must not be removed from its designated opening nor plugged.

The temperature-pressure relief valve must be installed directly into the fitting of the water heater designed for the relief valve. Position the valve downward and provide tubing so that any discharge will exit only within 6 inches (153 mm) above, or at any distance below the structural floor, see Figure 16. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size

under any circumstances. Excessive length, over 30 feet (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve.

No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6 inch air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must

be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.

Water Damage Hazard

Temperature-pressure relief valve discharge pipe must terminate at adequate drain•

The Discharge Pipe:

Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.

Shall not be plugged or blocked.

Shall be of material listed for hot water distribution.

Shall be installed so as to allow complete drainage of both the temperature-pressure relief valve, and the discharge pipe.

Shall terminate at an adequate drain.

Shall not have any valve between the relief valve and tank.

13

Page 13
Image 13
Kenmore 153.33616 LookatthetopofthewaterheaterThecoldwaterinlet.is, Temperature-Pressure Relief Valve, Water Damage Hazard