120VAC Smoke Alarm with Exit Light
Architectural and Engineering Specifications
The smoke alarm shall be Kidde Unit 1285 or approved equal. It shall be powered by a 120VAC, 60Hz, 80mA source along with a 9V battery back up. The unit shall incorporate an ionization sensor with nominal sensitivity of 1.26%/ft. The temper- ature operation range shall be between 40˚F and 100˚F (4˚C and 38˚C) and the humidity operation range shall be 5% - 95% relative humidity.
The smoke alarm can be installed on any standard single gang electrical box, up to a 4” octagon junction box. The electrical connection (to the alarm) shall be made with a
The alarm shall include a safety light that shall be powered by a 9V alkaline battery. The safety light shall provide 15 minutes of pulsating light when the alarm is sounding. The alarm shall include a test button that will electronically simulate the presence of smoke and cause the unit to go into alarm. This sequence tests the unit’s electronics, battery and horn to ensure proper operation.
The unit shall include a piezoelectric horn that is rated at 85dB at 10 feet. The unit shall include the Hush® feature that silences the unit. By pressing the Hush® button, it will desensitize the unit for approximately 7 minutes if a nuisance condition occurs. The alarm will chirp every
The unit shall also include a low battery warning utilizing a brief alarm chirp every
The unit shall incorporate one red LED to indicate the alarm’s current status and mode of operation. The red LED will indicate one of two conditions:
Standby Condition: The red LED will flash every
Alarm Condition: When the alarm senses products of combustion and goes into alarm, the red LED will flash rapidly (one flash per second). The rapid flashing LED and pulsating alarm will continue until the air is cleared.
The unit shall incorporate one green LED to indicate the alarm’s current status and mode of operation. The green LED will indicate one of two conditions: Standby Condition: The green LED will be steady on, indication the presence of
AC power.
Alarm Condition: The green LED of an alarm that senses smoke will flash to indicate the memory condition. The memory will remain activated until it is reset by pushing the test button.
The unit shall at a minimum meet the requirements of UL217, NFPA72, (chapter 11 2002 edition), The State of California Fire Marshall, NFPA 101 (One and two family dwellings) Federal Housing Authority (FHA), Housing and Urban Development (HUD). It shall also include a
Unit Number 1285E
Installation of Smoke Alarm
The combination alarm should be installed to comply with all local codes having jurisdiction in your area, Article 760 of the National Electric Code, and NFPA 72. Make certain all alarms are wired to a single, continuous
FUSE OR CIRCUIT BREAKER
L
N
BLACK | RED |
|
WHITE |
|
|
First | Additional |
|
Alarm | Alarms |
|
Technical Specifications | ||
Unit Number: | 1285E |
|
UPC: | ||
Power Source: | 120VAC |
|
Sensor: | Ionization |
|
Audio Alarm: | 85dB at 10ft |
|
Temperature Range: | 40˚F (4.4˚C) to 100˚F (37.8˚C) | |
Humidity Range: | 5% - 95% relative humidity (RH) | |
Size: | 5.6” in diameter x 1.55” depth | |
Weight: | 1lb |
|
Interconnects: | Up to 24 Kidde devices | |
LED: | Green, receiving ac power | |
| Red, alarm mode | |
Warranty: | 5 year limited |
|
| 5.6" | 1.55" |
Ordering Information
Gift Box UPC: |
|
|
|
|
|
| |
Part |
|
| Dimensions |
| Case/ | Layers/ | Skid |
Number | I 2 of 5 | Pack Quantity | (w x d x h inches) | Weight | Skid | Skid | Weight |
|
|
|
|
|
|
|
|
1285** | N/A | Individual | 5.75 x 1.75 x 5.75 | 1lb | N/A | N/A | N/A |
|
|
|
|
|
|
|
|
1285E | 200 25417 01258 3 | Master Pack (12 units) | 5.5 x 11.75 x 11.75 | 12lbs | 84 | 7 | 1000lbs |
|
|
|
|
|
|
| |
**Not for sale by individual unit |
|
|
|
|
|
| |
|
|
|
|
|
| 1 | 12 |
|
|
|
|
|
| UNIT | MASTER PACK |
Distributed by:
1394 South Third Street, Mebane NC 27302