PLANNING YOUR INSTALLATION
PAGE 6
COMBUSTIBLE WALL CLEARANCE
WARNING: IT IS VERY IMPORTANT THAT YOU
OBSERVE THE MINIMUM CLEARANCES.
There are listed clearances for your stove which were
determined in a Laboratory test using various "classes"
of stove pipe or chimney. Minimums are first estab-
lished for the stove itself and increased based on how
much heat is transferred by each class of pipe.
Note: Manufactured (mobile) home installations require
the use of a Type L Vent Chimney connector only. Use
of a single wall flue pipe connection is not permitted.
UNITED STATES REQUIREMENTS
Residential Reduced Clearance
Use listed double wall chimney connector or Type L
vent pipe to the top of the stove. Clearances (Inches):
A. 13.6" C. 15" E. 15" *
B. 25" D. 6" F. 5" *
RESIDENTIAL STANDARD
Does not apply to manufactured (mobile) home in-
stallations. Using single wall connector pipe from the
stove top up to the chimney support box. Clearances
(inches):
A. 21.6" C. 18" E. 15" *
B. 25" D. 13.75" F. 7.75" *
MANUFACTURED (MOBILE) HOME CLEARANCE
NOTE: Manufactured (Mobile) home installations re-
quire the use of a double wall chimney connector be-
tween the stove and the chimney as specified below.
Use of a single wall flue pipe connection is not permit-
ted. Chimney must be Simpson Dura-Vent Dura/Plus
chimney with manufactured (mobile) home installation
kit (Dura-Vent part number 6DP-MH). Chimney connec-
tor between stove and chimney must be Simpson Dura-
Vent DVL close clearance connector pipe. Manufac-
tured (Mobile) Home installations must use a rain cap
with a spark arrester. Clearances (Inches):
A.13.6" C.15" E. 15" *
B.25" D. 6" F. 5" *
PROTECTED WALL CLEARANCE
Some local codes will allow reduced clearances when the
stove is installed adjacent to a protected wall system. The
variance must be approved by your local building official.
Normally, the protected wall system is defined as a non-
combustible material with a minimum of 1" air space be-
hind. Check your local building codes or with a qualified
installer (Ref. NFPA 211).
CANADA REQUIREMENTS
This appliance is not approved for installation into a
manufactured (mobile) home in Canada.
Residential Reduced Clearance
Use listed double wall chimney connector or Type L vent
pipe to the top of the stove. Clearances (Centimeters):
A. 44.5 cm C. 40.5 cm E. 51.0 cm *
B. 76.0 cm D. 25.5 cm F. 15.0 cm *
Residential Standard
Using single wall connector pipe from the stove top up to
the chimney support box. Clearances (Centimeters):
A. 62.5 cm C. 53.5 cm E. 51.0 cm *
B. 76 cm D. 42.5 cm F. 27.5 cm *
Corner Installation
Parallel Installation
* Note: E and F dimensions are measured to side of
stove below the projection of outer top.