
Chimney Height Requirements -
The vent termination height required is - USA,
Termination Cap Must Be
Listed To UL 641 or ULC S609
USA 1 Foot Minimum
CANADA 3 Feet Minimum
Termination height is measured above the highest point where it passes through the roof surface.
Figure 17 -
Chimney Height Requirements - Manufactured Homes
The chimney must extend 3 feet (.92 meters) above the level of roof penetration and a minimum of 2 feet (.61 meters) higher than any roof surface within 10 feet (3 meters) (see below). Check with your local building officials for additional requirements for your area.
Requires A Listed |
| Top Of Flue Must Be 2 | Top Of Flue Must |
Termination Cap * |
| ||
| Feet Higher Than Any Part | Be 3 Feet Higher | |
|
| ||
| Less than | Of Roof Within 10 Feet | Than Highest |
| Horizontal | Point Of Roof | |
| 10 Feet (3 m) | ||
|
| Penetration | |
|
| 2 Feet (610 mm) Min. |
|
| 3 Feet (914 mm) |
| 3 Feet |
| Minimum | 10 Feet | |
|
| (914 mm) | |
|
|
|
(3 m) | Min. |
|
m = meter
mm = millimeter
Figure 18 - Manufactured Home Chimney Height Requirements
To pass inspection in nearly any jurisdiction, the chimney must meet both safety and exhaust flow requirements. The (3 feet by) 2 feet by 10 feet rule applies to both masonry and factory built chimneys
* Ref. NFPA 211, Vents installed with a listed cap shall terminate in accordance with the terms of the cap’s listings.
12 | NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE |