CLEARANCES AND HEARTH PROTECTION - INSERT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Clean-Out

 

 

 

 

 

24-5/8Ó

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model ProÞle¨ 30 INS-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tee

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In the USA and Canada, the area below and directly in front of the Profile

 

ProÞle 30-2 INS

1

7-3/4

Ó

 

 

 

 

30 INS-2 fireplace insert must be an approved fireplace hearth or protected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

by a non-combustible hearth / floor protector with a minimum thickness

 

Recommended

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of 3/8” which has a thermal conductivity of k (per inch) = .84 or lower

 

clearance zone

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value (better thermal protection) or resistance of r (per inch) = 1.19 or

 

from the front of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

higher value. See Floor Protection / Hearth Extension Using Alternate

 

the appliance to

 

 

 

 

 

 

 

Top View

 

 

 

Material As Floor Protector on Page 5 which explains minimum thermal

 

combustibles is 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

protection requirements.

 

 

 

 

 

 

 

 

 

 

 

 

 

feet minimum.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The protected area must extend 6Ó to the front of the face of the ProÞle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32Ó

 

 

 

 

 

 

 

 

 

30 INS-2.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 6 - Fireplace Firebox Minimum

 

Size, Insert

 

 

 

ProÞle 30 INS-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A - Insert to side wall

 

 

 

6Ó (153 mm)

 

 

 

 

 

 

 

 

 

Trim

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

¨ 30-2 INS

 

 

 

 

B - Insert to side trim

 

 

 

1Ó (26 mm)

 

 

 

 

 

Mantel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ProÞle

 

 

 

 

C - Hearth extension

 

 

 

6Ó (153 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Side View

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D - Insert to mantel

 

 

 

18Ó (458 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E - Insert to top trim

 

 

 

1Ó (26 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 4 - Minimum Clearances To Combustibles

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ProÞle 30-2 INS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Trim

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Side Wall

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Top View

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 7 - Mantel and Trim Clearances, Insert

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

Hearth / Floor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protection

 

 

 

FIREPLACE WARNING LABEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(provided in accessory package)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 5 - Clearances, Insert

 

 

 

 

 

 

 

 

 

 

When installing

the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IFTHIS FIREPLACE INSERT IS BEING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ProÞle 30 INS-2 into a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALLED INTO A FACTORY BUILT FIREPLACE,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

factory built Þreplace or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THIS LABEL MUST BE PERMANENTLY

 

 

 

 

Masonry And Factory Built Fireplaces Ð ProÞle 30 INS-2

 

heatform,

the air

ßow

 

 

 

ATTACHEDTOTHE FIREBOX OFTHE

 

 

 

 

 

within and

around

the

 

 

 

 

FACTORY BUILT FIREPLACE.

 

 

 

 

The model Profile 30 INS-2 is approved for installation into a solid fuel

 

Þ replace shall not be

 

 

 

 

W A R N I N G

 

 

 

 

 

altered by the installa-

 

 

 

 

 

 

 

 

burning fireplace, either a masonry fireplace (built to UBC 37 or ULC S628

 

tion of the insert

(i.e.

 

 

THIS FIREPLACE HAS BEEN ALTERED TO

 

 

 

 

 

 

 

ACCOMMODATE A FIREPLACE INSERT AND

 

 

 

 

standards) or an approved factory-built / zero clearance fireplace (built

 

DO NOT BLOCK louvers

 

 

 

 

 

 

 

 

 

SHOULD BE INSPECTED BY A QUALIFIED

 

 

 

 

to UL 127 or ULC S610 standards). See Pages 17 and 18 for additional

 

or cooling

air inlet or

 

 

 

PERSON PRIOR TO RE-USE AS A

 

 

 

 

information on venting.

 

 

 

 

 

 

 

 

 

 

 

 

 

outlet ports, circulating

 

 

 

CONVENTIONAL FIREPLACE.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

air chambers in a steel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Fireplace Firebox Size

 

 

 

 

 

 

 

 

 

 

 

 

 

Þreplace liner or metal heat circulator). The factory built Þrebox must

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

accept the insert without modiÞcation other than removing bolted or

 

 

Height ...............................................20-1/8” (512 mm)

 

 

 

 

screwed together pieces such as smoke shelf / deßectors, ash lips,

 

 

Width @ Front...................................32” (814 mm)

 

 

 

 

screen or door tracks and damper assemblies. Any Þreplace compo-

 

 

(extends back 1-1/2”)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nent, which is removed, must be retained so they can be reinstalled

 

 

Width @ back...................................24-5/8” (626 mm)

 

 

 

 

to restore the Þreplace to its original operating condition. The removal

 

 

Depth ................................................17-3/4” (452 mm)

 

of any part must not alter the integrity of the outer shell of the pre-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

engineered Þreplace cabinet in any way. A Warning Label (provided

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

with appliance) must be installed in the Þreplace Þrebox so that it shall

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

be visible upon removal of the Þreplace insert (Warning Label shown

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in gray above). Use RTV high Temperature Silicone as an adhesive to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

afÞx the warning label.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE