INSTALLING OFFSETS
First, review the Offset Elevation Chart and Figure 38 for reference.
Step 1. Determine the offset distance where chimney is to pass through the first ceiling- dimension “A.” To find this point on your ceil- ing, first determine the center point for a verti- cal chimney following the instructions for ver- tical installation.
Measure height to the ceiling from the top of
Step 2. Proceed by using the Straight Up Instal- lation Instructions for cutting and framing ceil- ing and roof openings.
Note: See Framing and Dimension Chart for the sizes of the ceiling and roof openings. The size of the roof opening varies with the degree of pitch of the roof.
Offset Elbow Assembly
Offset elbows install the same as chimney sections. First, snap the inner section INTO the preceding inner section of flue. Check connec- tion by pulling up slightly to ensure a tight fit. Next, the outer sections snap lock OVER the preceding outer section of chimney. Again, check outer section by pulling up slightly to ensure proper connection is made.
Return Elbow Assembly
Return elbows install the same way as round terminations and stabilizers:
Step 1. Hold return elbow over top of last chimney section.
Step 2. Center inner slip section into inner flue
Step 3. Center
Step 4. Pull up slightly on return elbow to ensure locking joint has firmly engaged.
Step 5. Secure support straps to framing members by nailing under tension in sheer (Figure 39 ).
Return
Elbow
Figure 39
Note: The return elbow assembly performs the same function as a stabilizer. Consider this when determining the need for a stabilizer.
Note: Do not apply excessive pressure to any subsequent chimney section following return elbow assembly when installing. Ensure that each subsequent chimney section is securely attached by testing as noted above.
Combustion Air Kits
These appliances are equipped with an outside
After completing the installation of the op- tional combustion air vent system the actuator arm must be put in service and tested to ensure proper operation before completing any enclosure around the firebox. Failure to do so may result in extensive and costly rework.
The control lever that operates the outside combustion air valve has been
Operate the actuator through several cycles including the "lock position. Ensuring proper operation and freedom of movement. Return the actuator arm to the locked position.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Control
Lever
Figure 40
Gas Line Connection
Install a ¹⁄₂" (13 mm) gas supply line through fireplace wall for connection to a decorative gas appliance inside the firebox. Outside, the gas supply line must connect to a gas
CAUTION: PLUMBING CONNECTIONS SHOULD ONLY BE PERFORMED BY A QUALIFIED, LI- CENSED PLUMBER. MAIN GAS SUPPLY MUST BE OFF WHEN PLUMBING GAS LINE TO FIRE- PLACE OR PERFORMING SERVICE.
Always plumb gas line installation per local codes. Check all connections and test for gas leaks, using a gas leak test solution (also referred to as bubble leak solution).
Note: Using a soapy water solution (50% dish soap, 50% water) is an effective leak test solution but it is not recommended, because the soap residue that is left on the pipes/ fittings can result in corrosion over time. Never use an open flame to check for leaks.
This provision is intended for connection to a decorative gas appliance incorporating an au- tomatic
17