16 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
2
4
6
8
10
12
14
16
18
20
2
4
6
8
10
12
14
16
18
20
22
24
26
28
MIN. 24" VERT. PIPE SECT.
WITH 9" HORIZONTAL SECT.
8' MAX
30' MAX
30
19' 7" MAX VERT. WITH
8' HORIZONTAL
VERTICAL HEIGHT (FT)
2 4 6 8 2468
VERTICAL HEIGHT (FT)

HORIZONTAL DISTANCE (FT) HORIZONTAL DISTANCE (FT)

6' MAX
A B C D
RESTRICTOR POSITIONS
2’ (MIN) OF
VERTICAL PIPE
REQUIRED
BELOW
TERMINATION

Vertical Terminations

The diagram below shows all allowable combinations of
straight vertical and offset to vertical vent configurations
with vertical terminations. The termination must fall within
the shaded areas on the diagram. Use the restrictor positions
indicated. Offsets may consist of two 90° elbows OR four
45° elbows. The minimum termination height is 10 feet and
the maximum is 30 feet.
NOTE: Horizontal pipe requires 1/4” rise for every 12”
of run. Offsets must remain within max and min lines.
Vertical height is measured from the bottom of stove.

Horizontal Terminations

The shaded areas in the diagram below show all allowable
combinations of vent configurations with horizontal termi-
nations. Horizontal sections of pipe require 1/4” of rise for
every 12” of run. A second 90° or 45° elbow (in addition to
the first 90° elbow at the top of the vertical length of pipe)
is allowed as long as the overall length of the horizontal
run of pipe does not exceed those shown below. Use the
restrictor positions indicated. Note that if the termination
cap falls in the unshaded area, then no restrictor is installed
in the stove.
Figure 25 Figure 26