NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
4
This manual describes the installation and operation of these non-catalytic
wood heaters. These heaters meet the U.S. Environmental Protection
Agency’s emissions limits for wood heaters sold on or after July 1, 1990.
This heater has been developed, tested and constructed in accordance
with the requirements of UL 1482, ULC S628 and HUD standards and
is listed by OMNI Test Laboratories, Portland, OR. It has been approved
for residential and alcove installations.
The appliance is merely one component of a larger system. The other
equally important component is the venting system. This is necessary for
achieving the required flow of combustion air to the fire chamber and for
safely removing unwanted combustion by-products from the appliance.
If the venting system’s design does not promote these ends, the system
may not function properly. Poorly functioning venting systems may create
TESTING INFORMATIONDRAFT REQUIREMENTSSELECTING THE PROPER VENTING SYSTEMYour wood fireplace insert is dependent upon a properly functioning
chimney for optimum performance. It is a high efficiency appliance that
loses much less heat up the chimney than older appliances and fireplaces.
For this reason it is important to match the fireplace insert to the chimney.
The chimney has two functions:
1. It draws combustion air into the appliance (without air, no fuel will
burn) and
2. It exhausts combustion by-products. Your new appliance is what is
known as a “natural draft” appliance.
The appliance depends solely on the natural draft of the chimney system
to draw combustion air into the unit. Draft is the force that moves air
from the appliance up into the chimney. The amount of draft in your
chimney depends on the length of the chimney, local geography, nearby
obstructions and other factors. Too much draft may cause excessive
temperatures in the appliance (overfiring). Slow or inadequate draft
equals poor combustion and possible smoking problems. The following
are some conditions that may contribute to poor chimney draft:
1. A chimney too large for your appliance.
2. A chimney with not enough height to produce adequate draft.
3. A chimney with excessive height (this may allow exhaust to cool too
much before exiting, which will stall the rate the exhaust exits).
4. Offsets in the venting system are too restrictive (see Chimney Guide-
lines).
Inadequate draft will cause the appliance to leak smoke into the room
through the fireplace insert and the chimney connector joints.
Excessive draft may cause an uncontrollable burn or a glowing red
fireplace insert or chimney part.
Overfiring Damage - If the heater or chimney connector glows, you are
overfiring. Other symptoms may include: Cracking, warping or burning
out of components, plated accessories may turn color, stove glass may
develop a haze, which will not come off with cleaning.
Overfiring of a stove or fireplace insert is a condition where excessive
temperatures are reached, beyond the design capabilities of the appli-
ance. The damage that occurs from overfiring is not covered under the
manufacturer’s limited warranty.
Also see Troubleshooting on Page 17.
performance problems as well as be a safety hazard. A draft test should
read greater than .04’ W.C. (inches water column) and less than .08”
W.C. As per NFPA-211 standard (see paragraph below), the installer
must take into account all variables within the installation and install the
appliance in such a manner that satisfies the draft requirements of the
appliance. See Chimney Guidelines below to assist you in selecting the
proper venting system for your installation.
American National Standards Institute ANSI/NFPA 211, Standard for
Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances
- See Draft Section: A chimney or vent shall be so designed and con-
structed to develop a flow sufficient to completely remove all flue and
vent gases to the outside atmosphere. The venting system shall satisfy
the draft requirements of the connected appliance in accordance with the
manufacturer’s instructions.
Chimney Guidelines:
• This appliance requires approximately 12 feet minimum of “effective
draw” provided by the venting system. As a rule of thumb, every 90
degree total direction change in the venting will result in a loss of
approximately 5 feet of “effective draw.” Example: If two 45 degree
offsets are used, subtract 5 feet from the actual vertical vent height
to determine your “effective draw.” In this case if you had 14 feet of
vertical vent, the effective draw would only be approximately 9 feet
(14 ft. - 5 ft. = 9 ft.), therefore it may be necessary to add additional
height to the venting system.
• In well insulated and weather tight homes, it may be difficult to establish
a good draft up your chimney. The poor draft is caused by a shortage
of air in the house (see Negative Pressure Warning on Page 5).
Chimney Height RequirementsThe chimney must extend 3’ (.92m) above the level of roof penetration
and a minimum of 2’ (.61m) higher than any roof surface within 10’
(3m) (see below). Check with your local building officials for additional
requirements for your area.
To pass inspection in nearly any jurisdiction, the chimney must meet both
safety and exhaust flow requirements. The (3’ by) 2’ by 10’ rule applies
to both masonry and factory-built chimneys.
* Ref. USA - National Standard, NFPA 211-latest edition and Canada
National Standard CSA B365-01-latest edition. Vents installed with a
listed cap shall terminate in accordance with the terms of the cap’s
listings.
Figure 1 - Chimney Height Requirements
Less than
10' (3 m)
10'
(3 m)
3' (914 mm)
Min.
2’ (610 mm) Min.
(914 mm)
Min.
3'