Lennox International Inc 11K71 Replacement, Defrost Control Board, Time-Delay, Diagnostic LEDs

Models: 11K71

1 2
Download 2 pages 11.36 Kb
Page 2
Image 2
REPLACEMENT

 

 

REPLACEMENT

DEFROST CONTROL BOARD

 

 

 

PRESSURE

 

 

 

 

 

 

SWITCH

 

 

 

 

 

SAFETY CIRCUIT

 

 

 

 

 

CONNECTIONS

 

 

 

 

 

 

 

 

 

/

DIAGNOSTIC LEDs

 

 

 

 

 

 

CONNECTION

FOR

 

 

 

 

 

ONE OPTIONAL

SWITCH

 

 

 

DEFROST

INTERVAL

 

 

 

 

 

 

PS2

 

 

 

TIMING

PINS

 

 

 

 

 

 

 

PS1

 

 

 

 

 

 

 

 

 

 

24V TERMINAL

STRIP

CONNECTIONS

FOR

 

 

 

 

 

TWO OPTIONAL

 

 

 

CONNECTIONS

SWITCHES

 

SERVICE

LIGHT

 

 

[]

ps2

.......

ONNECT,ON

 

 

 

 

 

 

 

 

Psi

.........................

.........................

 

 

 

 

FIGURE 1

 

 

 

Time-Delay

The timed-off delay is five minutes long. The delay feature is provided to help protect the compressor in case of an interruption in power to the unit or when a pressure switch resets.

Pressure Switch Safety Circuit

The defrost control incorporates a pressure switch safety circuit that allows the application of up to two optional pressure switches; high pressure and/or loss

of charge. See figure 1. During a demand cycle, the defrost control will lock out the unit on the third

instance that the unit goes off on any pressure switch wired to this circuit. The diagnostic LEDs will display a pattern for a lockout pressure switch on the third

open pressure switch occurrence. See table 1. The unit will remain locked out until the switch is reset.

Remove factory-installed jumper before connecting optional pressure switches to control board. When two pressure switches are used, wire each switch to one set of terminals PS1 and PS2 on the defrost

control board. See figure 1. When only one pressure switch is used, wire the switch to the two outside terminals of the pressure switch connections.

NOTE: If not using a pressure switch, the

factory-installed jumper wire must be connected.

Diagnostic LEDs

The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition.

TABLE 1

 

 

DEFROST CONTROL BOARD DIAGNOSTIC LED

 

 

MODE

 

LED 1

LED 2

Normal

Operation/

Flash together

Flash together

Power

to board

 

with LED 2

with LED 1

_me

Delay

 

Alternating

Alternating

 

Flashes

Flashes

To Protect Compressor

 

 

 

 

with LED 2

with LED 1

Pressure

Switch

Open

Off

On

Pressure

Switch

Lockout

On

Off

Board

Malfunction

 

On

On

Page 2

Page 2
Image 2
Lennox International Inc 11K71 Replacement, Defrost Control Board, Time-Delay, Pressure Switch Safety Circuit, Onnect,On