Lennox International Inc (2/4)SA13 Electrical Access, Typical Wiring Connections, Thermostat

Models: (2/4)SA13

1 10
Download 10 pages 50.73 Kb
Page 5
Image 5
Electrical Access

Heater Power Entry Entry WARNING

Unit must be grounded in accordance with national and local codes. Failure to ground unit properly can result in personal injury or death.

Power supply to the unit must be N.E.C. Class 1, and must comply with all applicable codes. A fused disconnect switch should be field provided for the unit. The switch must be separate from all other circuits.

If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring

diagram. Electrical wiring must be sized to carry minimum circuit ampacity marked on the unit. Use copper conduc- tors only. Each unit must be wired with a separate branch

circuit and be properly fused.

Electrical Access

Heater Power Entry Thermostat

Thermostat Typical Wiring Connections

Entry

Line Voltage

Entry

Figure 5

Thermostat

The room thermostat should be located on an inside wall where it will not be subject to drafts, sun exposure, or heat from electrical fixtures or appliances. Follow the

Typical Wiring Connections

THERMOSTAT

OUTDOOR UNIT

 

R

R

 

C

C

ECONOMIZER

Y

Y

 

 

NOT

 

 

INSTALLED

W

W1

 

W2

 

 

 

G

G

CAUTION

 

 

Do not connect C connections except when

 

 

required by the indoor thermostat. Refer to the

 

 

thermostat installation instructions.

 

 

 

L2

L1

GROUND

SCREW

POWER WIRING

208/230-1-60

(90°C MIN. WIRE)

POWER WIRING

24V CONTROL WIRING (NEC CLASS 2)

*W1, W2 CAN BE USED TO STAGE ELECTRIC HEAT ACCESSORY ON 15 & 20 KW MODELS.

*5 & 10 KW HEATER ACCESSORY FUNCTION OFF W1 ONLY.

TYPICAL WIRING CONNECTION

1 PHASE

THERMOSTAT

 

OUTDOOR UNIT

ECONOMIZER

 

R

 

R

 

 

C

 

C

BLUE

 

Y1

 

 

WHITE

 

 

 

Y

YELLOW

 

W

 

W1

 

 

 

W2

 

 

 

 

 

 

G

 

G

GREEN

CAUTION

 

 

 

 

Do not connect C connections except when

Y2

 

 

BLACK

required by the indoor thermostat. Refer to the

 

 

 

 

thermostat installation instructions.

L3

L2

L1

 

 

 

 

 

GROUND

 

 

 

 

SCREW

 

POWER WIRING

200/230-3-60, 460/575-3-60

(90°C MIN. WIRE)

POWER WIRING

24V CONTROL WIRING (NEC CLASS 2)

*W1, W2 CAN BE USED TO STAGE ELECTRIC HEAT ACCESSORY ON 15 & 20 KW MODELS.

*10 KW HEATER ACCESSORY FUNCTION OFF

W1 ONLY.

TYPICAL WIRING CONNECTION

3 PHASE

Figure 6

# 48392M005

Page 5

Page 5
Image 5
Lennox International Inc (2/4)SA13 warranty Electrical Access, Typical Wiring Connections, Thermostat, Entry, Page