14 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Figure 17

Figure 18

1. If any of the original wire as supplied must be replaced,
1. it must be replaced with Type AWM 105°C – 18 GA. wire.
2. 120V, 60Hz – Less than 3 amps.
BK
Junction Box
Transf.
120 V.
24 V
Factory Wired Field Wired
BL
Electronic Wiring Diagram (Honeywell)
Showing the Blower Wiring for the Optional
FBK-100 and FBK-200 Kits
R
W
BL
OPT
BLOWER
G
W
*OPTIONAL
ACCESSORY
SWITCH
120
VAC.
BK
W
Gas Valve
B
R
IGNITER
PILOT
ASSEMBLY
Break Off
Tab
BK
G
*Blower speed control switch is provided in FBK200 blower kit.
Outlet Box
Green Ground
Screw
Hot side of Outlet
Schematic Representation Only
**ON/OFF Switch (Integral
with Gas Valve)
**Leave the ON/OFF switch, which is integral
with the gas valve, in the ON position.
Red
pigtail
Black
pigtail
White Wire
to Opposite
Side
G
LIMIT SWITCH
OPTIONAL WALL SWITCH
OR OPTIONAL THERMOSTAT OR
OPTIONAL REMOTE RECEIVER
BK BK
1. If any of the original wire as supplied must be replaced,
1. it must be replaced with Type AWM 105°C – 18 GA. wire.
2. 120V, 60Hz – Less than 3 amps.
BK
Junction Box
Transf.
120 V.
24 V
Factory Wired Field Wired
BL
Electronic Wiring Diagram (Honeywell)
Showing the Blower Wiring for the Optional
FBK-250 Kits
R
BL
OPT
BLOWER
G
W
120
VAC.
BK
W
Gas Valve
B
R
IGNITER
PILOT
ASSEMBLY
BK
Outlet Box Green
Ground Screw
Hot side of Outlet
Schematic Representation Only
*ON/OFF Switch (Integral
with Gas Valve)
White Wire
To Opposite
Side
Optional FBK-250
Module
*Leave the ON/OFF switch, which is integral
with the gas valve, in the ON position.
OPTIONAL ON/OFF SWITCH,
WALL SWITCH, THERMOSTAT
OR REMOTE CONTROL RECEIVER
G
W
LIMIT SWITCH
BK BK

Figure 19

OPENING CONTROL
COMPARTMENT DOOR
Control
Valve
Lower Control
Compartment
Door
Open the lower panel or louver assembly by
pushing in the right side of the panel or louver
assembly and then lowering it forward and
down.

Step 6. CONNECTING GAS LINE

All codes require a shut-off valve mounted
in the supply line. The orientation of the
shut-off valve should face the front. Figure
20 illustrates two methods for connecting the
gas supply. A Sediment Trap is recommended
to prevent moisture and debris in gas line from
damaging the valve.
The flex-line method is acceptable in the U.S.A.
where local codes permit, however, Canadian
requirements vary depending on locality. Instal-
lation must be in compliance with local codes.
These appliances are equipped with a gas flex-
line for use in connecting the unit to the gas line.
See Figure 20 for flex-line description. The
flex-line is rated for both natural and propane
gas. A manual shut off valve is also provided
with the flex-line.
The gas control valve is located in the lower
control compartment.
To access the valve open the lower control
compartment door (see Figure 19).
The millivolt control valve has a 3/8" (10 mm)
NPT thread inlet port. The electronic control
valve has a 1/2" (13 mm) NPT thread inlet
port and is fitted with a 1/2" x 3/8" (13 mm x
10 mm) NPT fitting.
2. If the factory-provided outlet/junction box at
the right rear of the fireplace is being used,
remove the outlet box from the junction box
by removing two screws.
3. Connect the power supply wires (includ-
ing the ground supply wire) as shown in
Figures 17 and 18. (If the field-provided
J-box/outlet box is being used, all of the
outlet box wiring must be field-provided).
4. Locate and install a low voltage (24V)
wall-mounted switch or thermostat (both
field-provided) in the desired location.
5. Connect the low voltage wire, located in
the lower control compartment, to the wall-
mounted switch or thermostat.
Note: The supplied 15 feet of 2 conductor wire
has one end of each conductor connected
to the gas valve circuit and the other end of
each conductor placed inside the control
compartment.
6. Insert the control circuit plug into the un-
switched receptacle of the outlet box.
7. After wiring is complete, mount the outlet
box to the J-Box.
Note: The gas valve-mounted ON/OFF switch
is shown in Figures 17 and 18. It is integral
with the gas valve and should be set to the
ON position.

Step. 5 WIRING - OPTIONAL FORCED

AIR BLOWER KIT

FBK-100, FBK-200 and FBK250 Kits
(See Figure 17 for FBK-100, FBK-200 and
Figure 18 for FBK-250 wiring) -
An electrical outlet box (receptacle) is factory
-provided for the installation of the FBK-100,
FBK-200 and FBK-250 forced air blower kits.
(An optional field-provided outletbox/J-Box
may also be used. Electrical power must be
connected to either of these receptacles in order
to operate these blowers. Install the blower
kits according to the installation instructions
provided with the kits.
Note: The tab connecting the receptacles of
the outlet box must be broken in FBK-100 and
FBK-200 blower kit applications. See Figure
16 on page 13. Secure all joints tightly using appropriate
tools and sealing compounds (ensure propane
resistant compounds are used in propane ap-
plications). It is recommended to seal around
the gas line to prevent cold air leakage.
Acquire the shut-off valve and gas lex line and
pull the assembly forward out of the compart-
ment. Separate the shut-off valve from the gas
flex-line. Determine the length of pipe needed
to route the gas line from the last fitting (shown
in Figure 20 on Page 15) to a point within the
control compartment that will allow the shut-
off valve to be easily attached by hand to the
gas flex-line.