LG Electronics 5CSV2-03A Installation on the floor, After Installing, reassemble detached parts

Models: 5CSV2-03A

1 91
Download 91 pages 6.36 Kb
Page 66
Image 66

15. Installation

3) Installation on the floor

Installation of Mount Bracket.

• Select and mark the position for Mount Brackets and the piping hole.

Drill the hole for the anchor nut on the wall.

Drill the piping hole using a ø 70 hole-core drill.

Secure the Mount Brackets on the wall with four M4 screws.

Install the indoor unit onto the Mount Brackets.

Engage the slot at the back of the unit with Mount Bracket.

Drill the piping hole with 70mm dia, hole core drill.

Piping hole should be slightly slant to the outdoor side.

From the left wall

 

more than 760mm

 

 

From the

 

right wall

 

more than 840mm

Slot

448mm

Floor mount

bracket

Wall

 

Indoor

Outdoor

 

5~7mm

After Installing, reassemble detached parts.

Hang the 'Inlet Grille' and hook the 'Inlet Hanger' to the Hanger Screw.

Assemble the 'Side Plates(R,L)' with 2 screws on both left and right side.

Slot

Wall

Floor mount

bracket

Install plate

Piping hole

Ceiling & Floor, Ceiling Suspended (50Hz, R22) 65