Service Manual 75
Check the resistanceTroubleshooting Guide
Error Title Cause of error Check point & Normal condition
code
44 Outdoor air sensor
45 Condensor pipe sensor
47 D-Pipe sensor
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
Normal resistor : 10KΩ/ at 25°C(77°F) (Unplugged)
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)
Normal resistor : 5KΩ/ at 25°C
(77°F)
(Unplugged)
Normal voltage : 2.5Vdc / at 25°C
(77°F)
(plugged)
Normal resistor : 200KΩ/ at 25°C
(77°F)
(Unplugged)
Normal voltage : 4.5Vdc / at 25°C
(77°F)
(plugged)
❑Check Point
1. Estimate the resistance of each sensor.(Unplugged)
2. Estimate the voltage of each sensor.(Plugged)
3. If the resistance is 0V or 5Vdc, then sensor is abnormal
Ω
Ω