CHIMNEY 30° OFFSET THROUGH FLOOR OR CEILING
It may be necessary to assemble the chimney at 30° when passing through the floor or ceiling area. Use the F8FS30 firestop spacer as shown in Figures 31 & 32. Support the chimney at floor or ceiling penetration with a FTF8 stabilizer if distance of chimney below ceiling is 10' or more. Maintain 1"* minimum air space to combustibles from chimney sections.
Attic Space |
|
F8FS30 | 1"* Min. |
Firestop Spacer | |
| Air Space |
1"* Min. | |
Air Space |
|
10' |
|
Max. | 30 Firestop |
Figure 31 | And Attic Above |
Room Above |
|
F8FS30 | 1"* Min. |
Firestop Spacer | |
| Air Space |
1"* Min. | |
Air Space |
|
10' | 30 Firestop |
Max. | And Room Above |
Figure 32
For Canada Only
When installing the chimney system through an open attic space, the attic shield assembly- firestop spacer must be used (Figure 33). This installation is required only for use in Canada.
Open Attic Space
Figure 33
Note: For Canadian installations, all chimney installed outside the building must be constructed with galvalume (outer sections only). The appropriate model designations are located in the back of this manual.
Step 4. Note: Chimney sections are constructed with a unique locking tab design, which ensures an immediate, tight assembly between sections. Plan your chimney requirements carefully before assembly as chimney is difficult to disassemble after installation. If disassembled, the tabs might become damaged. Be certain tabs are properly formed to ensure locking tabs engage properly.
The Security Chimney's FTF8 chimney system is a two piece chimney, which snap together from the fireplace up. Start with the inner flue section with the lanced end up, snap lock it in to the matching collar on top of the fireplace. At all subsequent joints, the upper flue section fits into the preceding flue section. Each piece snaps together by means of locking tabs (9 locking tabs per joint). Check each piece by pulling up slightly from the top to ensure proper engagement before installing the next section. If the flue has been installed correctly, it will not separate when you test it. Also, the inner flue joint where each section is joined should be tight and flat without gaps (Figure 34).
Figure 34
The outer chimney section installs the opposite- way; the lanced end goes down and each new section goes OVER the outside of the previous section installed (Figure 35).
Locking Tabs (Lances)
Figure 35
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Note: Assemble one component of chimney at a time (inner section first, then outer section last) before proceeding with the next complete section.
Continue to assemble the chimney up through framed opening. Assemble just enough to penetrate the roof flashing openings (Figure 36). Always maintain 1"* minimum air space to insulation and construction materials. Always check each chimney joint (inner and outer) to ensure proper engagement. Check vertical alignment of chimney so that it projects from the roof in true vertical position.
1"* Min. Air Space
To Combustibles
Figure 36
Security's chimney sections do not need to be screwed together. Additional reinforcement is not necessary except in certain offset conditions (refer to Page 16, Figure 47).
Step 5. The height of vertical chimney pipe supported only by the fireplace must not exceed 30'. Chimney heights above 30' must be supported by a Model
Note: The Model
Install the Model
*Notes:
•2" clearance to combustibles required in Canada.
•Outdoor installations less than 15’ height require chimney clearance of 2” air space to insulation and construction materials.
13