If the terminus of the last section is not within this distance, use the telescopic vent section SV4.5LA, as the last vent section. For wall thicknesses greater than that shown in Figure 28, refer to Table 3 on page 18. This table lists the additional venting components needed (in addition to the termination and adapter) for a particular range of wall thicknesses.
M. Attach termination adapter - Attach the adapter (SV4.5RCH - provided with the termi- nation) to the vent section or telescoping vent section), elbow as shown in Figure 27 in the same manner as any SV4.5 vent component (refer to Step F).
N. Install Firestop/Spacer at exterior wall -
When using the square termination, install the SV4.5HF (Secure Vent) or SF4.5HF (Se- cure Flex) Firestop/Spacer over the open- ing at the exterior side of the framing (long side up) as shown in Figure 27, and fasten into place. Ensure 5" clearance is main- tained by framing above the vent run for MPLDV35/40/45 when center line of the run is lower than 48" (12119 mm) above
Firestop/Spacer provided with the termination shown on the exterior side of the wall. It may also be
installed on the interior side.SV4.5
| **7" | ||
| (178) | ||
(267 mm) | |||
| |||
(308 mm) |
|
|
(130 mm)
**3” (76 mm) for MPLDV30/35
6 to 48 inch |
| 1" |
Vent Section, |
| |
| (25.4 mm) | |
Telescopic vent |
| |
section on Elbow |
|
|
| Note: Centerline of Vent Piping is | |
| NOT the Same as the Centerline of | |
Adapter | the Frame Opening. |
|
| See Figure 9 on page 8 | |
SV4.5RCH |
| |
|
| for Min. Distance to Base |
**Increase these dimensions by 2” (51mm) for MPLDV35/40/45 | of Appliance. | |
| ||
with horizontal vent runs with center lines lower than 48” | Base of Appliance | |
(1219mm) above the fireplace for wrapper surface. |
Figure 27 Installing the Square Horizontal Termination (SV4.5HT-2)
the fireplace top wrapper surface.
(The Firestop/Spacer may also be installed over the opening at the interior side of the framing.)
O. Install the desired termination -
1. Install the square termination |
For the last step , from outside the exterior wall, |
slide the collars of the termination onto the |
*Use silicone caulking to seal the top and sides of the termination, up to the underlayment, stucco, or masonry wall surface.
Siding
*Caulk
Interior Surface of
Finished Wall
Maximum Extent of Vent Run Sections Relative to Exterior Surface of Framing
Last Vent Section. Use T e l e s c o p i c V e n t Section (SV4.5LA), If Necessary
Maximum wall thickness 10 in.(254 mm)**
Exterior Surface of Siding
Exterior Surface of
Framing
6 in. to
SV4.5HT-2
adapter (the outer over the outer and the inner |
inside the inner) until the termination seats against |
the exterior wall surface to which it will be |
attached. Orient the housing of the termination |
with the arrow pointed upwards. Secure the |
termination to the exterior wall. The horizontal |
termination must not be recessed into the |
exterior wall or siding by more than the |
(32 mm) as shown in Figure 28. |
*Caulk
Adapter
SV4.5RCH
Stucco | **For thicknesses greater |
than 10”, see Table 3. |
Square Termination
Square Termination into
Exterior Finishing Material
SVHRK Snorkel Cap
IMPORTANT: The vent termination is hot while in operation and for a period of time following use of the fireplace. To prevent contact with hot surfaces, we recommend the use of a Termination Guard. This can be purchased at your local dealer.
Venting Connection and Exterior Wall Recessing of the
Horizontal Square Termination
Figure 28
Horizontal terminations have been designed to perform in a wide range of weather conditions. Our terminations meet or exceed industry standards.
When selecting the locations of your horizontal terminations, do not place the termination where water from eaves and adjoining rooflines may create a heavy flow of cascading water onto the termination cap. If the cap must be placed where the possibility of cascading water exists, it is the responsibility of the builder to direct the water away from the termination cap by using gutters or other means.
Take care to carefully follow the installation instructions for the termination, including the use of silicone caulking where required.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. | 17 |