12
8. Secure front of the equipment to rack mounting rails to prevent the
equipment from sliding out of position. If securing holes are provided
on front of the equipment that align with the center holes on return
flange of front members, you can use the four (4) extra M5 screws
provided in this kit to secure the equipment. Otherwise, the equip-
ment should be secured to front of rack mounting rails with four (4)
customer-supplied fasteners.
9. To orient the display for horizon-
tal viewing, remove the front
plastic bezel by pulling forward
evenly on both sides. The unit
has two front panel overlays.
Remove the outer overlay (used
for tower installation). This
reveals a horizontally oriented
front panel overlay for rack
mounting. Snap the front bezel
back into place.
10. Once the UPS is installed in the
rack, the load may be con-
nected. Ensure the load equip-
ment is turned off; plug all loads
into the output receptacles on
the rear of the UPS.
11. Plug the UPS into a dedicated
wall receptacle properly pro-
tected by a circuit breaker or
fuse in accordance with national
and local electrical codes. Use a 20 amp rated device for the 2700VA,
208V unit. The wall receptacle must be grounded.
12. Turn ON the UPS by pressing the ON button; then turn on the con-
nected load equipment. The UPS is now providing conditioned power
to your equipment.
+
UPStation GXT
AC INPUT BATTERY UPS ON BYPASS
+
UPStation GXT
AC INPUT BATTERY UPS ON BYPASS
Vertical
overlay
for
tower
UPS
Horizontal overlay
for rack UPS