The Liebert® GXT3UPS is ready to be powered.

1.Locate the plastic bezel from the shipping box and attach the bezel to the UPS taking care to align the fastening clips on both ends before inserting them into the holes.

2.If your application requires the use of external battery cabinets for longer back up time requirements, connect the first battery cabinet to the UPS with the cable provided with the battery cabinet. Note: Either connector is acceptable to connect the external battery cabinet. If more than one battery cabinet is used the additional cabinets then connect to the previously connected battery cabinet.

3.Ensure the maintenance bypass breaker is in the open position and that the guard is secured in place.

4.Ensure that the REPO connector on the rear of the unit has a jumper between pins 1-2 of the REPO connector or properly wired to an Emergency Power Off circuit (normally closed).

5.Install any optional Intellislot communication card into the Intellislot port on the rear of the unit.

6.Close the input breaker in the panelboard that provides input power to the UPS

7.Close the input breaker on the rear of the UPS unit. Note: The UPS will now have power and the AC Input indicator on the display will illuminate. The UPS will begin to charge the internal batteries causing the battery capacity LEDs to illuminate.

8.The Liebert GXT3 UPS has customizable settings that might be required depending on the application. Please review the CD that ships with the UPS unit for the steps to use the configuration program and make any necessary changes. Once that is complete, proceed to the next step.

9.Close all output breakers on the rear of the UPS

10.If external battery cabinets are used, close all breakers on the rear of each battery cabinet

11.Press and hold for about 4 seconds, the “ON” button on the UPS display. Note: this will apply power to the output receptacles via the internal bypass. The bypass indicator will be illuminated along with an audible beep during this time.

12.Over the next several seconds the UPS will perform the self checks and then automatically transfer the connected equipment to conditioned power. Once that is complete, the bypass indicator will turn off and the inverter indicator will illuminate.

The UPS is now running in normal operation mode providing protected, filtered power to the connected equipment.

6000VA

3SLI-23185QS6_Rev0_09-2012

Page 3
Image 3
Liebert 5000RT230, 6000RT230 quick start 3SLI-23185QS6Rev009-2012

5000RT230, 6000RT230 specifications

The Liebert 6000RT230 and Liebert 5000RT230 are advanced uninterruptible power supplies (UPS) designed to safeguard critical electronic equipment from power disturbances and ensure uninterrupted operation. These models are ideal for applications in data centers, telecommunications, and industrial environments that require high reliability and power management.

One of the primary features of the Liebert 6000RT230 and 5000RT230 is their double-conversion online architecture. This technology provides a continuous supply of clean, reliable power by converting incoming AC power to DC and then reconverting it back to AC. This process ensures that the output power is free from surges, sags, and electrical noise, providing maximum protection for sensitive loads.

These UPS systems are equipped with highly efficient power management capabilities, featuring an efficiency rating of up to 94%. This high level of efficiency not only reduces operational costs but also minimizes heat generation, contributing to a lower overall environmental impact. Additionally, both models are designed with a compact footprint and can be easily integrated into existing infrastructure without requiring significant modifications.

Another notable characteristic is their advanced monitoring and management features. The Liebert 6000RT230 and 5000RT230 come with a user-friendly LCD display that allows users to easily monitor the status of the UPS, including input/output voltage, battery status, and load levels. They also support various communication protocols, including SNMP and USB, enabling seamless integration into network management systems.

The battery management technology in these UPS models ensures optimal battery performance and longevity. The built-in predictive diagnostics help in identifying potential issues before they lead to failures, allowing for timely maintenance. Furthermore, the hot-swappable battery feature allows for battery replacement without shutting down the load, ensuring that operations remain uninterrupted.

Both models offer flexibility in deployment, with options for rack-mounted or tower configurations, making them suitable for different environments and user preferences. The Liebert 6000RT230 model offers higher capacity options, making it particularly suitable for larger setups that demand more power.

Overall, the Liebert 6000RT230 and 5000RT230 are reliable, efficient, and feature-rich UPS solutions that provide robust power protection for critical applications, ensuring operational continuity and safeguarding investments in technology.