AC8 Specifications

AC8 Specifications

Power

 

 

 

 

115VAC Transformer Module / UML11500

 

230VAC Transformer Module / UML23000

Requirements

 

 

 

 

 

 

 

115VAC ±10% of nominal; 60Hz, 4A, 460VA

 

230VAC ±10% of nominal; 50Hz, 0.5A, 115VA

Dimensions: W x D x H, in. (mm)

 

 

18 x 2-3/4 x 18 (457.2 x 69.85 x 457.2)

Weight (Assembled)

 

 

 

20.56 lb. (9.33 kg)

Enclosure Type

 

 

 

NEMA 1

Liquid Crystal Display (LCD)

 

 

Four line, 20 character, backlit

Mounting Surface

 

 

 

Building Wall or Structural Member

Ambient Operating Environment

 

32ºF to 104ºF (0ºC to 40ºC) 0% RH to 95% RH (non-condensing)

Processor Specifics

 

 

 

 

 

 

Model

 

 

 

 

 

Motorola XC68HC812A4

Clock speed

 

 

 

16MHz

Total RAM

 

 

 

256Kb

Total FLASH

 

 

 

 

4M

Total EEPROM

 

 

 

 

4K

A/D Resolution (Analog IN)

 

 

12 Bit

Modem Type Embedded

 

 

14.4K bps

Clock Type

 

 

 

Real-Time Clock

Clock battery backup type

 

 

Lithium Cell (non-replaceable)

Clock battery life

 

 

 

7 years, constant, no power

Modem battery backup type

 

 

Nickel Cadmium (replaceable)

Modem battery life

 

 

 

10 minutes at full load

Communications

 

 

 

 

 

 

Local Communications

 

 

 

RS232

Remote: Modem (9600-N-8-1)

 

Baud rate 9600 bps, Parity=None, Data bits=8, Stop bits=1

Remote: Supported pagers

 

9600 E-7-1 supports TAPI protocol version 1.8

SiteScan Web

 

 

 

IGM Protocol, EIA422

Agency Listings

 

 

115VAC Transformer Module (TM115)

 

230VAC Transformer Module (TM230)

UL

 

 

 

 

UL1012

 

 

UL1585

CSA

 

 

 

 

 

C22.2 No. 66 and C22.2 No. 107.1

CE

 

 

 

 

 

 

Yes

FCC Compliance

 

 

 

 

N/A

Inputs & Outputs (Quantity)

 

 

 

 

 

Digital Inputs (8)

 

 

 

Dry Contact Closure 24VDC, 10 mA

Analog Inputs (4)

 

 

4-20 mA signal input with selectable power source of 12VDC or 24VDC

Digital Outputs (8)

 

 

 

24VAC, 3A

Common Alarm Outputs (2)

 

 

24VAC, 3A

Ordering Information

 

 

 

 

 

 

 

 

 

 

Quantity

Part #

 

 

 

 

Description

 

 

 

 

 

AC8L115

 

AC8 controller board & Transformer Module 115VAC with two 24VAC outputs (40VA each) and 115VAC

 

 

receptacle in enclosure

 

 

 

 

 

 

 

 

 

 

AC8L230

AC8 controller board & Transformer Module 230VAC with two 24VAC outputs (40VA each) in enclosure

 

201258P1

 

RS232 configuration cable

 

 

 

 

TW420

 

Temperature Transmitter Wall 4-20 mA @ 45°F to 96°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liebert Corporation

 

 

 

 

 

 

1050 Dearborn Drive

Telephone: 1-800-877-9222

 

 

 

 

P.O. Box 29186

Facsimile: 1-614-841-6022

 

 

 

 

Columbus, OH 43229

www.liebert.com

© 2005 Liebert Corporation

All rights reserved throughout the world. Specifications subject to change without notice.

®Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

SL-31101 (12/05) Rev. 0

4

Page 4
Image 4
Liebert AC8 Specifications, Ordering Information, Liebert Corporation, Dearborn Drive, Telephone, P.O. Box, Facsimile