Installation
2.2Liebert NX UPS to Non-Liebert NX UPS
! WARNING
Installation by qualified electrical personnel
1.Connect the power cables of the adapter to the Phase A, Neutral and Ground Output of each UPS.
2.Connect the LBS cable to COM1 of the LBS Signal Adapter connected to the Liebert NX.
3.Connect the other end of the LBS cable to X4 on the parallel board (UHW241M3) in the NX UPS.
4.Connect the communication cable (up to 492 ft. [150m]) to the COM2 interface of each LBS Signal Adapter.
5.The switches of LBS signal adapters connected to the Liebert NX should be in the right position and the switches of LBS signal adapters connected to the
Figure 5 Connecting a Liebert NX to a non-NX UPS
Power ON COM1 | COM2 SWITCH |
| Power ON COM1 | COM2 SWITCH |
|
LED1 | LED1 |
Power Cable
Connect to NX UPS
LBS
Cable
Power Cable
Connect to
Communication Cable
up to 492 ft. (150m)
Table 1 | Human | |
Item |
| Description |
|
| |
Power port | Connect to Phase A, Neutral and Ground of output of UPS. | |
LED1 (red) | Power LED. It illuminates when the power is on, turns off when the power fails. | |
|
|
|
COM1 |
| LBS Signal interface. |
| Connect to NX series UPS unit. | |
|
| |
|
| RS485 interface. |
COM2 |
| Connect to other Signal Adapter. |
| Green LED: Communication Power is OK. | |
|
| |
|
| Yellow LED: Adapter is connected to Non NX series UPS. |
|
|
|
SWITCH |
| Switch to left: Connect to |
| Switch to right: Connect to NX series UPS unit. | |
|
|
Table 2 | Electrical rating | |
|
| |
Description | Rating | |
|
|
|
Voltage |
| |
Frequency |
| |
|
|
|
Current |
| 0.2A Max |
|
|
|
Table 3 | Part number description | |
Description | Part Number | |
|
| |
150 Meter Kit | NX150MLBSKIT | |
50 Meter Kit | NX050MLBSKIT | |
|
|
|