40 Appendix 3 Product Specification
E1-20010329-C-1.0
Capacity 10kVA 15kVA 20kVA
Model GXT2-3X1
-0100L
GXT2-3X1
-0150L
GXT2-3X1 -0200L
Bypass Voltage 120~253Vac (non- ECO mode)
Efficiency in
Normal Mode
(100% Linear
Load)
> 89% > 89% > 89%
Efficiency in
battery mode
(100% Linear
Load)
> 88% > 88% > 88%
interrupt
time
Utility Failure 0ms
Transferring
between inverter
and Bypass
(Synchronized )
< 4ms
Voltage transient response At the Resistive Load from 0~100% or 100%~0, the Output dynamic
voltage change range is lower than 5% Rated Voltage. Transient recovery
time is less than 60ms.
Audible Noise < 55dB(1m) < 60dB(2m)
Display LCD
Safety Passed CCEE certification,complied with EN60950 and EN50091-1.
Highest Input Voltage : Line Voltage 554Vac,1 hour(static)
EMC Conduction:EN55022 Class A
Radiation: EN55022 Class A
Harmonic current:THD<25%(With input isolated transformer connected)
Immunity EN61000-4-2.3.4.5.6.8.11 Level III
DC offset Lower than ±500mVdc
MTBF(Inverter ) 30000 hours (ambient temperature is 25℃,rated condition)
MTBF(System) 150000 hours (Response time + maintenance time should be less than 24
hours)
MTTR (Board Maintenance) 1 hour(Board Maintenance)
Insulation Resistance > 2MW (500Vdc)
dielectric Strength ( Output to earth,
Input to earth )
2820Vdc,leakage current<3.5mA, 1min
with no arc and breakdown
Surge Protection Satisfy the IV type of IEC60664-1, that is the ability to withstand
1.2/50uS+8/20uS exceeds 6kV/3kA.
Protection Level IP21