LRTTM Battery Cabinet Specifications

LRTTM Battery Cabinet Specifications

Model Number

GXT96VLRT2UL

Compatible With

1800RT-208, 2000RT-120, 2000RT-230, 2700RT-208,

UPStation GXT:

3000RT-120 and 3000RT-230 VA UPS’

DIMENSIONS: in. (mm)

 

Unit W x D x H

15 x 27 x 29 (381 x 686 x 737)

WEIGHT: lbs (kg)

 

Unit

600 lbs (272kg)

INPUT AC PARAMETERS

 

Voltage Range

85 to 265VAC

Frequency

>40 to <70 Hz; auto sensing

Input Power Factor

>0.95

Current Reflected THD

30% THD maximum

Current Rating

< 4A at 120VAC, < 2A at 230VAC

Input Power Connection

IEC320-C14 recessed plug, with input cords:

 

(1) 6’ cord with NEMA 5-15P

Fuse Rating

6.3 A

OUTPUT DC PARAMETERS

Output Sockets

(2) per LRT cabinet

Interconnect Cable

(1) 9.8’ (3m) cable with appropriately keyed plugs

Protection

(1) resettable DC circuit breaker

BATTERY PARAMETERS

 

Type

Valve-regulated, nonspillable, lead acid

Quantity x Voltage x

8 x 12V x 65.0Ah

Rating

 

Approved Battery

CSB, Panasonic, and Yuasa

Manufacturers:

 

Recharge Time

<20 Hours to 95% capacity after full discharge into 100% load

ENVIRONMENTAL

 

Operating Temperature

+32° F to + 104° F (0° C to +40° C) for altitudes

 

0 to 5,000 ft (1,500m);

 

+32° F to + 95° F (0° C to +35° C) for altitudes

 

5,000 ft (1,500m) to 10,000 ft (3,000m)

Storage Temperature

+5° F to + 122° F (-15° C to +50° C)

Relative Humidity

0% to 95%, non-condensing

Audible Noise

< 45 dBA, at 1 meter

AGENCY

 

Safety

UL 1778; c-UL Listed; EN 50091-1; CE low voltage directive

Surge

IEEE 587 Category A; EN61000-4-5,

 

Level 3 (L-E), Level 2 (L-L)

ESD

EN6100-4-2, Level 3

Susceptibility

EN6100-4-3, Level 2

Electrical Fast

EN6100-4-4, Level 3

Transient/Burst

 

Immunity

EN50082-1

EMI/EMC

FCC Part15, Class A; EN50081-1; EN 55022, Class B;

 

CE EMC Directive