Liebert PS048A specifications ETL/CSA certified ISO 9001 certified company

Models: PS048A

1 2
Download 2 pages 61.72 Kb
Page 1
Image 1
•ETL/CSA certified.

Keeping Business in Business

Process Fluid Chiller Designed for Marconi Medical MX8000

Dedicated, equipment-matched cooling supplies the proper temperature and water flow year round.

Factory-tested, piped, wired and charged for hassle-free startup and operation.

Clean, non-ferrous cooling loop, required for sensitive medical equipment.

Local service and parts for quick and knowledgeable maintenance and service.

Optional switch-over to alternate water source provides redundant, continuous operation.

Optional remote monitoring systems keep you informed of chiller operation.

ETL/CSA certified.

ISO 9001 certified company.

MX8000 Specifications

 

 

 

 

 

 

 

 

 

 

 

 

Fluid Specified

 

Water or Glycol

 

 

 

 

 

 

 

 

 

 

Max Heat Dissipation—BTUH (kW)

 

32,400 (9.5)

 

 

 

 

 

 

 

 

 

 

Fluid Temperature Range—°F (°C)

 

36-57 (2-14)

 

 

 

 

 

 

 

 

 

 

Temperature Gradient

 

 

0.5°C/min

 

 

 

 

 

 

 

 

 

 

Fluid Flow Rate—GPM (l/m)

 

4.4 (16.7)

 

 

 

 

 

 

 

 

 

 

Fluid Pressure Drop—PSI (kPa)

 

2.2 (15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Process Fluid Chiller Specifications

 

 

 

 

 

 

 

Model Number

 

PS048A

 

PS048A

PS048A

 

 

 

 

 

 

Fluid Circulated

 

Water

 

Ethylene Glycol

Propylene Glycol

 

 

 

 

 

 

Net Cooling Capacity—BTUH (kW)

 

41,200 (12.1)

 

38,300 (11.2)

36,500 (10.7)

 

 

 

 

 

 

Leaving Fluid Temperature—°F (°C)

 

48 (8.9)

 

48 (8.9)

48 (8.9)

 

 

 

 

 

 

Fluid Flow Rate—GPM (l/m)

 

8 (30.4)

 

8 (30.4)

8 (30.4)

 

 

 

 

 

 

MX8000 Pressure Drop—PSI (kPa)

 

2.2 (15.2)

 

2.2 (15.2)

2.2 (15.2)

 

 

 

 

 

 

Chiller Pressure Drop—PSI (kPa)

 

8.2 (56.5)

 

11.1 (76.5)

13.1 (90.3)

 

 

 

 

 

 

Pump Total Head—PSI (kPa)

 

46.8 (322.7)

 

46.8 (322.7)

46.8 (322.7)

 

 

 

 

 

 

Head Available for Piping Circuit—PSI (kPa)

 

36.4 (251)

 

33.5 (231)

31.5 (217.2)

 

 

 

 

 

 

Pump HP (kW)

 

1 (0.75)

 

1 (0.75)

1 (0.75)

 

 

 

 

 

 

 

Process Fluid Chiller Designed for Marconi Medical MX8000

1

Page 1
Image 1
Liebert PS048A specifications ETL/CSA certified ISO 9001 certified company