3.11Alarm Messages
:KHQýWKHýGHIDXOWýVFUHHQýLQVWUXFWVý\RXýWRý&KHFNý0HVVDJHVñýSUHVVýWKHý'RZQýSDGýWRýVHHýWKHý$ODUPý 0HVVDJHVýVFUHHQïý$FWLYHý$ODUPý0HVVDJHVýZLOOýEHýGLVSOD\HGýDORQJýZLWKýDýVHTXHQFHýQXPEHUýDQGý WLPHýRIýRFFXUUHQFHïý1RWHýWKDWýWZRýRUýPRUHý$ODUPý0HVVDJHVýFDQýKDYHýWKHýVDPHýVHTXHQFHýQXPEHUý ZKLFKýPHDQVýWKH\ýRFFXUUHGýVLPXOWDQHRXVO\ïý&RQWLQXHýSUHVVLQJýWKHý'RZQýSDGýXQWLOýDOOýDFWLYHý $ODUPý0HVVDJHVýKDYHýEHHQýGLVSOD\HGï
7DEOH åýVKRZVý$ODUPý0HVVDJHVýõZLWKýUHODWHGýDODUPVýJURXSHGýWRJHWKHUôýDQGýRSHUDWRUýFRUUHFWLYHý DFWLRQñýLIýDQ\ïý&RQWDFWý/LHEHUWý&XVWRPHUý6HUYLFHýDQGý6XSSRUWýDWýìðåííðèéêðëêæåýLIý\RXýUHTXLUHý DVVLVWDQFHïý
Table 8 | Alarm Messages | |
|
| |
Alarm | Meaning and | |
Message | Corrective Action in Brackets [ ] | |
AC INPUT |
|
|
|
| |
Input power out of tolerance | Frequency or voltage of the input power is outside the acceptable range. The | |
|
| battery supplies power to the critical load through the UPS Module. |
|
|
|
DC BUS |
|
|
|
| |
Charger in reduced current mode | Customer has selected reduced current operation of the charger from a contact | |
|
| external to the UPS. |
|
| |
Battery charger problems | The battery is not being charged. The voltage produced by the charger is | |
|
| insufficient to maintain a charge on the battery. |
|
| [Contact Liebert Customer Service and Support at |
|
| |
Low battery warning issued | Battery has been discharging and the Low Battery Warning Time (factory set at | |
|
| 5 minutes, adjustable range 1 to 99 minutes) has been reached. Note time |
|
| stamp on alarm message. |
|
| [Follow appropriate procedures to shut down the critical load in an orderly |
|
| sequence.] |
|
| |
Low battery shutdown | Battery has discharged to the minimum allowable voltage and the UPS is shut | |
|
| down. No power is being supplied to the critical load. |
|
| [When input power becomes available, perform a UPS |
|
|
|
DC bus overvoltage |
| DC bus voltage has exceeded the specified limit and the charger has been |
|
| turned off. The charger will automatically restart when the DC bus voltage |
|
| returns to within tolerance. |
|
| [Contact Liebert Customer Service and Support at |
|
| condition persists for more than 2 minutes.] |
|
|
|
BYPASS |
|
|
|
| |
Bypass frequency out of tolerance | Input power frequency is outside of the specified tolerance (adjustable range .5 | |
|
| to 5 Hz). Automatic transfers to the Static Bypass Line are prohibited. |
|
| [Do not operate the Rotary Switch while this condition is present.] |
|
| |
Load transferred to bypass due to | Critical load connected to the UPS has exceeded the UPS power rating. The | |
overload |
| load has been automatically transferred to the Static Bypass Line. Power to the |
|
| load is not being conditioned by the UPS. An automatic retransfer will be |
|
| attempted when the load is reduced. |
|
| [Determine cause of the overload and reduce the load.] |
|
| |
Load transferred to bypass due to DC | DC bus voltage has exceeded the specified limit. The load has been | |
overvoltage |
| automatically transferred to the Static Bypass Line. An automatic retransfer will |
|
| be attempted when the DC bus voltage returns to within tolerance. |
|
| [Contact Liebert Customer Service and Support at |
|
| condition persists for more than 2 minutes.] |
|
| |
Excessive retransfers attempted | Several automatic retransfer attempts (15 attempts during 20 minutes or less) | |
|
| have been made to retransfer the load from the Static Bypass Line back to the |
|
| UPS. The UPS has not been able to consistently sustain the load because of |
|
| an overload condition or an inverter failure. The load will remain on the Static |
|
| Bypass Line. Power to the load is not being conditioned by the UPS. |
|
| [Check other messages for inverter failure. Determine cause of the overload |
|
| and reduce the load.] |
|
|
|
Static Switch failure |
| A fault has been detected in the Static Transfer Switch. Automatic transfers to |
|
| the Static Bypass Line are prohibited. |
|
| [Contact Liebert Customer Service and Support at |
|
|
|
58 Operation