Total Recovery Ventilator | Model 195TRV/300TRV |
|
|
ENGINEERING DATA
MOTORS AND BLOWERS - Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation.
120 VAC, 1.5 Amps.
FILTERS - Washable air filters in exhaust and supply air streams.
MOUNTING THE TRV - Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST - Damper defrost system.
DEHUMIDISTAT - Adjustable Internal Dehumidistat.
CASE - Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS - ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, Recirculation mode (on compatible units), (each mode has 5 speeds). Control pad can be removed from HRV and remotely mounted.
WEIGHT 106 lbs. (48 kg) SHIPPING WEIGHT 108 lbs. (49 kg)
PERFORMANCE
Net supply airflow in cfm (L/s) against external static pressure
| 195TRV | 300TRV | ||
E.S.P | cfm | L/s | cfm | L/s |
@ 0.1” (25 Pa) | 203 | (96) | 265 | (125) |
@ 0.2” (50 Pa) | 191 | (90) | 260 | (123) |
@ 0.3” (75 Pa) | 182 | (86) | 250 | (118) |
@ 0.4” (100 Pa) | 167 | (79) | 235 | (111) |
@ 0.5” (125 Pa) | 155 | (73) | 220 | (104) |
|
|
|
| |
VAC @ 60HZ | 120 |
| 120 | |
|
|
|
| |
WATTS / Low speed | 100 |
| 150 | |
|
|
|
| |
WATTS / High speed | 173 |
| 333 | |
|
|
|
|
|
Amp rating |
| 1.5 |
| 2.9 |
|
|
|
|
|
| 195TRV5DCS FANCURVE |
| 5 | HIGH SPEED* |
| ||||
| 225 |
|
|
|
|
| 4 | MEDIUM HIGH SPEED | |
|
|
|
|
|
|
| |||
| 200 | 5 |
|
|
|
| 3 | MEDIUM SPEED | |
|
|
|
|
| 2 | MEDIUM LOW SPEED | |||
|
|
|
|
|
|
| |||
(cfm) | 175 | 4 |
|
|
|
| 1 | LOW SPEED |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| ||
150 | 3 |
|
|
|
|
|
|
| |
Flow | 125 | 2 |
|
|
|
|
|
|
|
Air | 100 |
|
|
|
|
|
|
|
|
| 1 |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
| 75 |
|
|
|
|
|
|
|
|
| 50 |
|
|
|
|
|
|
|
|
| 0.1 | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 |
Static Pressure (in H20)
300TRV0DCS FANCURVE |
|
|
5 HIGH SPEED* |
| 300 |
|
|
|
|
|
| 4 | MEDIUM HIGH SPEED | |
|
|
|
|
|
|
|
| |||
| 275 | 5 | *Manufacturers Data |
|
| 3 | MEDIUM SPEED |
| ||
| 250 |
|
| 2 | MEDIUM LOW SPEED | |||||
(cfm) |
|
|
|
|
|
|
| 1 | LOW SPEED |
|
225 | 4 |
|
|
|
|
|
|
|
| |
200 | 3 |
|
|
|
|
|
|
|
| |
Flow |
|
|
|
|
|
|
|
| ||
175 | 2 |
|
|
|
|
|
|
|
| |
Air | 150 | 1 |
|
|
|
|
|
|
|
|
| 125 |
|
|
|
|
|
|
|
|
|
| 100 |
|
|
|
|
|
|
|
|
|
| 75 |
|
|
|
|
|
|
|
|
|
| 0.1 | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 | 1 |
Static Pressure (inH20)
DIMENSIONS 195TRV/300TRV inches (mm)
STALE
TO
P o r t s
6 "( 1 5 0m m )
FRESH
FROM
DEFROST
DAMPER
| METALCLASPS | MOTOR |
| HRV | ERV |
| Core | Core |
|
| 49 " |
| CONDENSATE | (1245) |
|
| |
DEFROST | DRAINS |
|
FROM |
|
|
STALE
FROM
P o r t s
7 "( 1 7 8m m )
BLOWERS
FRESH
TO
19" | (483) |
*NOTE:
Frontclearance
of25inches(635mm) isrecommended
forservicingunit.
143/4"
(375)
OPTIONS
includes Programmable Time Clock and Dehumidistat
mounted Control Pad
remotely mounted Control Pad.
1 Kw, 7” (178 mm)
mesh screen
WARRANTY Units carry a LIFETIME warranty on the heat recovery core, a five year warranty on the ERV core and a 5 year replacement parts warranty.
All units conform to CSA and UL standards.
TRV Sales Sheet
Revised: 06/07