Specifications

Model CAF-U-S4A-24-P16

Core

Filters

Case

Ventilation system has patented aluminum heat recovery core (standard) or an enthalpic energy recovery core (optional) for energy-efficient ventilation. Enthalpic cores are recommended for regions where the temperature does not drop below 25˚F (-4˚C).

Washable air filters in exhaust and supply air streams of ventilation section, 1" pleated in return plenum side.

Prepainted galvanized steel for superior corrosion resistance.

Dimensions & Clearances

SideFront

Model

CAF-U-S4A-24-P16

Voltage

120 VAC 60 Hz

Top

16"

12"

Ventilation

4" 6" Supply Air

Inlet

Latches

Hp

1/3

 

 

Amps (total)

7

 

 

Water

1/2" Copper Soldered

Connections

Connection

19"

17.25"

Supply Air

 

29.5"

Note: Ventilation ports and return plenum opening available off either side of cabinet. All units conform to CSA

Ventilation

6" Exhaust Air

Outlet

 

22"

14"

Return Air

 

29.5"

Blower Section

19"

47.5"

 

Airflow (High)

1030 CFM

 

.25 in wg

 

.5 in. wg

890 CFM

 

 

 

 

 

Ventilation

100 - 140 CFM

 

Airflow

 

 

 

 

 

 

 

Effectiveness

70%

 

 

(Aluminum Core)

 

 

 

 

 

 

 

Total Efficiency

50%

 

 

(Enthalpic Core)

 

 

 

Net Weight

150 lbs.

 

 

 

 

 

Shipping Weight

165 lbs.

and UL Standards.

(SERVICE CLEARANCE 1') (SERVICE CLEARANCE 3')

Options

99-186

Weatherhoods, Two - 6" c/w

 

1/4" mesh screen

99-130W

Remote Wall Mount Dehumidistat

 

Control 24 VAC only

99-RSK6

6” back draft damper

99-104

DET - Digital Electronic Timer

Warranty

Units carry a lifetime warranty on the heat recovery (aluminum) core, a five year warranty on the energy recovery (enthalpic) core and a five year replacement parts warranty on all other components.