Lifebreath CAF-02-MB installation manual Option 2 Ventilation Ports Off Right Side, Ducting

Models: CAF-02-MB

1 44
Download 44 pages 46.61 Kb
Page 23
Image 23

Option 2 - Ventilation Ports Off Right Side

Upflow Models

Remove circular metal knockout

Remove styrofoam knockout

Downflow Models

Remove styrofoam knockout

Remove styrofoam knockout

Horizontal Models

Remove circular metal knockout

Penetrations from sheet metal screws used to fasten the ductwork to the cabinet of the unit should only be placed into the duct flange provided. This is to avoid contact and damage of the heating/air conditioning coils and internal wiring.

Ducting

The duct sizing for the furnace section can be determined using HRAI Residential Air System Design Manual, SMACNA, or any other industry- recognized manuals.

Note: "Combo units" normally deliver air at approx. 110°F (43°C), and therefore may require larger than normal ductwork. When installing the Clean Air Furnace as a replacement unit on a retrofit application, always calculate the size of duct that is there.

Any ductwork running through unconditioned space must be sealed properly and insulated to prevent heat loss. All local codes must be followed in determining the amount of insulation needed.

The ventilation section consists of two 6" (15.2cm) round ports located on the side of the cabinet, which vent to the outside. Insulated ducting with a vapour barrier such as flex-ducting, or ridged pipe wrapped in pipe sleeve, is required to prevent condensation from occurring on the pipe. Also the airflow in these lines is designed to be balanced. (See "Balancing Airflows" in this manu- al, for damper location and procedure).

Warning: A backdraft damper is required in the exhaust air duct to prevent cold air from entering the unit when the Clean Air Furnace is not running.

23

Page 23
Image 23
Lifebreath CAF-02-MB installation manual Option 2 Ventilation Ports Off Right Side, Ducting