SURGICAL PERIMETER LUMINAIRE SUS SERIES 432/632
Page 4 of 4 | 2'x4' RECESSED FLUORESCENT, ASYMMETRIC/SYMMETRIC ACRYLIC LENS |
| RFI SHIELDED, 4 OR 6 LAMP, T8 OR T12 |
| MODEL NO. SUS2GFSMA432120O4 |
61.2% EFFICIENT
coefficients of utilization — zonal cavity method
RF |
| 20 |
|
| 20 |
|
| 20 |
|
RC |
| 80 |
|
| 50 |
|
| 30 |
|
RW | 70 | 50 | 30 | 50 | 30 | 10 | 50 | 30 | 10 |
| 1 | 68 | 65 | 63 | 61 | 59 | 58 | 59 | 57 | 56 |
| 2 | 62 | 58 | 54 | 55 | 52 | 50 | 53 | 51 | 49 |
| 3 | 58 | 52 | 48 | 49 | 46 | 43 | 48 | 45 | 42 |
| 4 | 53 | 47 | 42 | 44 | 40 | 37 | 43 | 40 | 37 |
| 5 | 49 | 42 | 36 | 40 | 35 | 32 | 38 | 35 | 32 |
| 6 | 45 | 37 | 32 | 36 | 31 | 28 | 35 | 31 | 28 |
| 7 | 42 | 34 | 29 | 32 | 28 | 25 | 31 | 28 | 25 |
| 8 | 38 | 30 | 25 | 29 | 25 | 22 | 28 | 24 | 21 |
| 9 | 35 | 27 | 22 | 26 | 22 | 19 | 25 | 21 | 19 |
10 | 33 | 25 | 20 | 24 | 19 | 17 | 23 | 19 | 16 | |
|
|
|
|
|
|
|
|
|
|
Black housing exterior | Fully gasketed |
for cooler ballast | lens frame |
operating temperature |
|
Hemmed over
Black striped interior perimeter of body eliminates light leak
Symmetrical distribution | Asymmetrical distribution |
The footcandle readings of a typical 8' x 12' pattern layout of 8, 4 lamp units, illustrates that the asymmetric distribu- tion adds 35% more light to the operat- ing area (room size 12'
x 16' x 9' ceiling.
A silver grid printed on the back of the asymmetric lens, grounded to the fix- ture,
prevents RFI interference with other equipment.
To prevent any EMI leakage,
the housing is sealed and the lens frame is fully gasketed.
F Type fixtures cannot butt together end to side. A space
is required between fixtures (See dia- grams below).
F TYPE | F TYPE | F TYPE |
(Concealed | (Concealed | (Concealed |
Spline) | Spline) | Spline) |