Lightolier Coefficients Of Utilization, Calculite Incandescent Surface Cylinder 7018AO, Type

Models: 7018AO

1 2
Download 2 pages 6.68 Kb
Page 2
Image 2
Calculite® Incandescent Surface Cylinder 7018AO

Calculite® Incandescent Surface Cylinder 7018AO

Page 2 of 2

 

80

 

 

 

 

 

 

Clear Alzak with 150W A21

 

 

 

 

 

 

 

 

 

 

2880 Lumens Per Lamp

 

 

FOOTCANDLES

70

 

 

 

 

 

 

RCR = 1 (60' x 60' x 8.5' room)

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

RCR = 5 (12' x 12' x 8.5' room)

 

 

 

 

 

 

 

RCR = 10(6' x 6' x 8.5' room)

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

Room Surface Reflectances:

 

 

 

 

 

 

 

 

 

80% Ceiling; 50% Walls; 20% Floor

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INITIAL

30

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

20

40

 

60

80

100

120

140

160

180

 

 

 

 

 

AREA PER FIXTURE IN SQUARE FEET

 

 

 

3

4

5

6

7

8

9

10

11

12

13

14

 

 

 

CENTER TO CENTER DISTANCE OF FIXTURES IN FEET

Use quick calculator chart to determine spacing of luminaires for desired level of illumination.

Conversion Factors:

100W A21, F.C. X 0.6

Spacing Ratio = 1.1

150W A21

 

 

 

90

CANDLEPOWER SUMMARY

DEG

CP

ZONAL FLUX

 

0

1319

0

 

5

1266

120

300

15

1080

306

60

25

1130

523

 

 

35

588

369

600

45

421

326

 

55

123

110

 

65

6

6

900

75

2

2

85

0

0

 

 

90

0

0

30

 

 

 

1200

 

ZONAL SUMMARY

 

 

6” Aperture A Lamp / BR30 / PAR38

 

80

 

 

 

 

 

 

Clear Alzak with 100W PAR38 FL

 

 

 

 

 

 

 

 

 

 

1400 Lumens Per Lamp

 

 

 

 

FOOTCANDLES

70

 

 

 

 

 

 

RCR = 1 (60' x 60' x 8.5' room)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

RCR = 5 (12' x 12' x 8.5' room)

 

 

 

 

 

 

 

 

 

RCR = 10 (6' x 6' x 8.5' room)

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

Room Surface Reflectances:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80% Ceiling; 50% Walls; 20% Floor

 

 

INITIAL

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

40

 

60

80

100

120

 

 

 

 

 

 

AREA PER FIXTURE IN SQUARE FEET

 

 

 

3

4

5

6

 

7

8

9

10

11

CENTER TO CENTER DISTANCE OF FIXTURES IN FEET

Use quick calculator chart to determine spacing of luminaires for desired level of illumination.

Conversion Factors:

PAR38 FL: 100W(IR), F.C. X 1.5; 120W, F.C. X 1.4; 90W, F.C. X 0. 70W/60W(IR), F.C. X 0.8

BR30 FL: 85W, F.C. X 0.6 (S.R.=0.9); 75W, F.C. X 0.5 (S.R.=0.9);

Spacing Ratio = 0.4

 

 

150W A21

CANDLEPOWER SUMMARY

DEG

CP

ZONAL FLUX

 

90

0

4932

 

5

4382

404

 

 

10

3249

 

 

15

1805

541

400

20

777

 

25

373

196

60

30

173

 

 

 

 

35

72

57

800

40

45

 

45

38

30

 

 

50

34

 

 

55

29

20

1200

60

0

 

65

0

0

 

 

70

0

 

30

75

0

0

80

0

 

1600

85

0

0

 

90

0

 

 

ZONE

LUMENS

LAMP

FIXT

ITL, Inc. report No. 21590

0-30

949

32.9

53.8

Date: 2-9-77

0-40

1318

45.8

74.8

Efficiency: 61.2%

0-60

1754

60.9

99.5

0-90

1763

61.2

100.0

 

 

90-180

0.0

0.0

0.0

 

0-180

1763

61.2

100.0

Tested According to IES proce- dures. Test distance exceeds five times the greatest luminous open- ing of Luminaire.

Certified test report No. 0847FR Computed by LSI program

Efficiency = 89.3%

 

ZONAL SUMMARY

ZONE

LUMENS

LAMP

FIXT

0-30

1141

81.56

91.37

0-40

1198

85.64

95.94

0-60

1249

89.25

99.99

0-90

1249

89.26

100.00

40-90

50

3.63

4.06

60-90

0

.01

.01

90-180

0

.00

.00

0-180

1249

89.26

100.00

COEFFICIENTS OF UTILIZATION

% EFFECTIVE CEILING CAVITY REFLECTANCE

 

 

 

 

80

 

 

 

70

 

 

50

 

 

30

 

 

 

10

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

30

10

 

 

 

% WALL REFLECTANCE

 

 

 

50

30

10

0

 

 

 

 

50

30

10

50

30

10

50

30

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

.68

.66

.65

.66

.65

.64

.64

.63

.62

.62

.61

.60

.59

.59

.58

.57

RATIO

2

 

.63

.61

.58

.62

.60

.58

.60

.58

.57

.58

.57

.55

.56

.55

.54

.53

3

 

.59

.56

.53

.58

.55

.53

.56

.54

.52

.55

.53

.51

.53

.52

.50

.49

4

 

.55

.51

.49

.54

.51

.48

.53

.50

.48

.51

.49

.47

.50

.48

.47

.46

CAVITY

 

5

 

.51

.47

.44

.50

.47

.44

.49

.46

.44

.48

.45

.43

.47

.45

.43

.42

6

 

.47

.43

.41

.47

.43

.41

.46

.43

.40

.45

.42

.40

.44

.42

.40

.39

ROOM

7

 

.44

.40

.37

.43

.40

.37

.42

.39

.37

.42

.39

.37

.41

.38

.36

.35

8

 

.41

.37

.34

.40

.36

.34

.39

.36

.34

.39

.36

.34

.38

.35

.33

.33

9

 

.37

.34

.31

.37

.33

.31

.37

.33

.31

.36

.33

.31

.35

.33

.31

.30

 

 

 

10

 

.35

.31

.28

.35

.31

.28

.34

.31

.28

.34

.30

.28

.33

.30

.28

.27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20% FLOOR CAVITY REFLECTANCE

 

 

 

 

 

 

 

 

 

COEFFICIENTS OF UTILIZATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

% EFFECTIVE CEILING CAVITY REFLECTANCE

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

70

 

 

50

 

 

30

 

 

 

10

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

30

10

 

 

 

% WALL REFLECTANCE

 

 

 

50

30

10

 

0

 

 

 

 

 

 

 

50

30

10

50

30

10

50

30

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

1.01

1.00

.99

1.00

.98

.97

.96

.95

.94

.93

.92

.91

.90

.89

.89

 

.87

 

RATIO

2

 

 

.97

.95

.93

.96

.94

.92

.93

.92

.90

.91

.89

88

.88

.87

.86

 

.85

 

3

 

 

.94

.91

.89

.93

.90

.88

.91

89

.87

.89

.87

86

.87

.86

.85

 

.84

 

 

 

 

 

 

CAVITY

4

 

 

.91

.88

.86

.90

.88

.85

.89

.86

.84

.87

.85

.83

.85

.84

.83

 

.82

 

6

 

 

.86

.83

.81

.85

.82

.80

.84

.82

.80

.83

.81

.79

.82

.80

.79

 

.78

 

ROOM

5

 

 

.88

.85

.83

.87

.84

.82

.86

.84

.82

.85

.83

.81

.84

.82

.80

 

.79

 

7

 

 

. 83

.80

.78

.83

.80

.78

.82

.79

.78

.81

.79

.77

.80

.78

.77

 

.76

 

 

8

 

 

.81

.78

.76

.81

.78

.76

.80

.77

.76

.79

.77

.75

.79

.77

.75

 

.74

 

 

9

 

 

.79

.76

.74

.79

.76

.74

.78

.76

.74

.78

.75

.73

.77

.75

.76

 

.73

 

 

10

 

 

.77

.75

.72

.77

.75

.72

.77

74.

72

.76

.74

.72

.76

.73

.72

 

.71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20% FLOOR CAVITY REFLECTANCE

 

 

 

 

 

 

 

 

 

 

 

 

Conversion Factor: 45W TO 120W PAR 38 FL, C.U. X 1.0. 65W TO 85W BR30 FL, C.U. X 0.85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Job Information

 

Type:

 

 

 

 

 

 

 

 

 

 

 

Lightolier a Genlyte Thomas Company

 

 

 

 

 

www.lightolier.com

 

 

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710

 

 

We reserve the right to change details of design, materials and finish.

 

 

 

 

 

© 2004 Genlyte Thomas Group LLC (Lightolier Division) • B0704

 

 

 

 

 

Page 2
Image 2
Lightolier Coefficients Of Utilization, Calculite Incandescent Surface Cylinder 7018AO, Page 2 of, Job Information