Wiring Options: 2 Circuit Center/Outer Switching

 

Lighting SystemsBaselyte-BSL2

Page of 8

3 Light T8 Direct/Indirect

Wiring Options: 2 Circuit Center/Outer Switching

2 Circuit Center/Outer Switching

Type 2: 2cct.

Type 9: 2cct. w/1cct. thru wire

Type I: 2cct. w/2cct. thru wire



















Fixture wired for two circuit. Lamps wired for center/outer switching.

2 Circuit Center/Outer Switching with Emergency Circuit/Night Light (EC/NL)

Type 4: 2cct. w/EC/NL





%#.,





%#.,





%#.,

One 4’ section in two circuit fixture (center/outer switching) to be wired on a separate thru circuit. Leads for both normal circuit and EC/NL circuit wired to fixture ends. All lamps in EC/NL section to be wired together.

2 Circuit Center/Outer Switching with Emergency Battery Pack (EM)

Type 6: Chloride standard C700A

Type N: Bodine standard B70A

Type F: Chloride high performance C1400

Type Q: Bodine high performance B50











 %-







Fixture wired for two circuits (center/outer switching), plus a battery pack is wired to one lamp. A hot lead is connected to the battery pack and would act as a ‘trigger’ wire when connected to a constant hot by installer. Leads for both normal circuit and battery pack are wired to fixture ends.

*Note: Multi-lamp battery packs are also available.

2 Circuit Center/Outer Switching with Emergency Circuit/Night Light and Emergency Battery Pack

Type K: Chloride standard C700A





%#.,





%#., %-





%#.,

One 4’ section in a two circuit fixture (center/outer switching) to be wired on a separate thru circuit, in addition, a battery pack is wired to one lamp. Installer can connect ‘trigger’ wire to EC hot lead if controlled together or wired separately if controlled independently. Leads for normal circuit, EC/NL and battery pack are wired to fixture ends. All lamps in EC/NL section to be wired together.

*Note: Multi-lamp battery packs are also available.