Lightolier Lighting Systems Baselyte-BSL26, Performance, Module Lengths & Mounting Distances

Models: Baselyte-BSL26

1 8
Download 8 pages 18.28 Kb
Page 2
Image 2
Lighting Systems  Baselyte-BSL26

Lighting SystemsBaselyte-BSL26

Page

 

of 8

 

 

 

 

 

 

 

Performance

 

 

 

 

 

 

 

Candlepower Curve

Candlepower Summary

 

 

 







 

 

 

ZONE

 

CANDLEPOWER

 

 

 

 

 

 

 

 

 



 

 

DEG.

0

22.5

45

67.5

90

 

 

 

 

 

 

 

 

 

 



 

 

180

2352

2352

2352

2352

2352

 

 

 

 



 

175

2339

2344

2352

2359

2363

 

 

 

 



165

2252

2281

2324

2362

2376

 

 

 

 



155

2092

2153

2252

2343

2374

 

 

 

 



145

1862

1966

2143

2269

2305

 

 

 

 

135

1572

1730

1970

2121

2163

 

 

 

 

 



125

1234

1460

1729

1899

1957

 

 

 

 

 



 

 

 



115

858

1119

1448

1621

1661

 

 

 

105

475

770

1082

1119

1139

 

 

 

 

 

 



 

 

 



95

113

267

458

389

406

 

 

 

 

 

90

5

4

13

6

8

 

 

 

 



 

 

 

 

 

 

85

0

0

0

0

0



 

 

 



 

 

 

 

 

 

75

0

0

0

0

0

 

 

 

 



 

 

 

 

 

 

65

0

0

0

0

0



 

 





 

 

 





 

 

55

0

0

0

0

0

 

 

 

Report No: 2101711

45

0

0

0

0

0

35

0

0

0

0

0

Lamps: F54T5

25

0

0

0

0

0

Lumens per Lamp: 4650

15

0

0

0

0

0

Efficiency: 96.9%

5

0

0

0

0

0

Up: 100.0% Down: 0.0%

0

0

0

0

0

0

Module Lengths & Mounting Distances

@

-ODULE ,ENGTH ,

-OUNTING $ISTANCE

@

-ODULE ,ENGTH ,-OUNTING $ISTANCE

@

-ODULE ,ENGTH ,-OUNTING $ISTANCE

Note: Shaded area indicates locations of emergency sections (emergency wiring controls all lamps or optional battery pack controls one or two lamps).

2 Light T5 HO Indirect

Coefficients of Utilization

 

 

% EFFECTIVE CEILING CAVITY REFLECTANCE

 

 

 

80

 

 

70

 

 

 

50

 

 

 

 

 

% WALL REFLECTANCE

 

 

 

 

50

30

10

50

30

10

 

50

30

10

0

91

91

91

78

78

78

 

53

53

53

1

79

76

73

68

65

62

 

46

44

43

2

69

64

59

59

55

51

 

40

38

35

3

60

54

49

52

46

42

 

35

32

30

4

53

46

41

45

40

35

 

31

28

25

5

47

40

35

40

34

30

 

28

24

21

6

42

35

29

36

30

26

 

25

21

18

7

37

30

25

32

26

22

 

22

18

15

8

34

27

22

29

23

19

 

20

16

13

9

30

24

19

26

20

17

 

18

14

12

10

27

21

17

24

18

15

 

16

13

10

Zonal Lumen Summary

 

 

ZONE

LUMENS

%BARE LAMP

%LUMINAIRE

0-90

0

0

0

90-180

8923

95.9

100.0

0-180

8923

95.9

100.0

Run Configuration

Run

4’

8’

12’

Joiner

End Set

Mount

Power

Length

Module

Module

Module

Mount*

 

 

 

 

 

 

 

 

 

 

 

4’ run

1

 

 

 

1

1

1

 

 

 

 

 

 

 

 

8’ run

 

1

 

 

1

1

1

 

 

 

 

 

 

 

 

12’ run

 

 

1

 

1

1

1

 

 

 

 

 

 

 

 

16’ run

 

2

 

1

1

2

1

 

 

 

 

 

 

 

 

20’ run

 

1

1

1

1

2

1

 

 

 

 

 

 

 

 

24’ run

 

 

2

1

1

2

1

 

 

 

 

 

 

 

 

28’ run

 

2

1

2

1

3

1

 

 

 

 

 

 

 

 

32’ run

 

1

2

2

1

3

1

 

 

 

 

 

 

 

 

*Note: Additional power mounts may be required for some runs with T5 HO lamping options, longer runs, and runs with wiring options that are more complex. Please consult factory for assistance.

System Components & Accessories

End Set

BSLESW = suspended standard white

Joiner

BSLJS = suspended joiner

Job Information

Type:

Lightolier a Genlyte Company

www.lightolier.com

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish.

© 2005 Genlyte Group LLC • 0205 Rev.1

Page 2
Image 2
Lightolier Lighting Systems Baselyte-BSL26, Performance, Module Lengths & Mounting Distances, Run Configuration, Type