Prismatic Lens

Fresnel Lens

Calculite® HID Lensed Downlight C7E17FL-PL

Page 1 of 2

 

7" Aperture, ED17 (Enclosed), Ceramic Metal Halide, Fresnel or Prismatic Lens

20" (508 mm) to 30" (762 mm)

8-1/4"

 

9-3/4"

(210 mm)

(248 mm)

 

 

10-1/2" (267 mm)

(473 mm)

18-5/8"

 

Top View

(Magnetic Ballast)

11 9

10-7/8" (276 mm)

8-3/4"

(222 mm)

2

5

3

1

4

7

8

6

11

12

10

20" (508 mm) to 30" (762 mm)

9-3/4"

(248 mm)

10-7/8" (276 mm)

11" (280 mm)

(100W)

Top View

(Electronic Ballast)

7-5/16" (187 mm) Dia.

8-5/8" (200 mm) Dia.

Vertical Adjustment: 5/8" (16 mm) to

2 7/8" (73 mm)

2" (50 mm) max. Ceiling Thickness

Ceiling Cutout: 8" (203mm) dia.

Reflector Trim

 

Frame-In Kit

Lamp (Coated, Ceramic MH)

C7E17FLWHW

Fresnel Lens, White Step Baffle, White Flange

C770MHE1

Electronic, 120V

70W

ED17,BD17

(Enclosed)

C7E17PLWHW

Prismatic Lens, White Step Baffle, White Flange

C770MHE2

Electronic, 277V

70W

ED17, BD17 (Enclosed)

C710MHE1

Electronic, 120V

100W

ED17, BD17 (Enclosed)

 

 

 

 

C710MHE2

Electronic, 277V

100W

ED17 BD17

(Enclosed)

 

 

C770MHU

Magnetic, 120V/277V

70W

ED17, BD1

(Enclosed)

 

 

C710MHU

Magnetic, 120V/277V

100W

ED17, BD17 (Enclosed)

 

 

 

 

 

 

 

Features

1.Reflector: Semi-Specular anodized aluminum, 16 ga. Removable from inside fixture for access to splices and ballast.

2.Lens: Prismatic (C7E17PLWHW) or Fresnel (C7E17FLWHW) lens. Regressed 1 3/4" from ceiling line.

3.Die-Cast Baffle: Painted white, self flange, deep conical step baffle for low brightness, supports lens. Small Allen-head set screw provides secure attachment for use where vandal resistant luminaires are required.

4.Torsiontite Springs: Permit removal of lens assembly without tools.

5.Socket Cup: Galvanized steel, pre-wired with medium base pulse rated socket. Snaps onto upper reflector for secure attachment without tools; unitized construction assures proper lamp alignment to optics for consistent performance.

6.Mounting Frame: 0.048"(18-ga.) galvanized steel includes pre-installed mounting bars.

7.Mounting Ring: 0.048"(18-ga.) galvanized steel. Designed for vertical adjustment from above or below for ceilings from 0" to 2" thick. Center-line notches allow consistent alignment of multiple fixtures.

8.Retaining Springs: Rust resistant simplify reflector housing removal for inspection and maintenance.

9.Vertical Adjustment Mechanism: Accommodates mounting to virtually any ceiling system using mounting bars (provided, or 1/2" EMT tubing (by others). Single locking feature secures all adjustments. Alignment holes and markings allow fixture to be preset prior to installation.

10.Mounting Bars: 0.048" (18-ga.) pre-installed, telescoping bars extend to 30" long and lock securely into position. Built-in locking tabs provide positive attachment to common T-bar systems. Self-centering feature simplifies instal- lation in 24" O.C. grid systems. Attaches to steel or wood joists without accessories.

11.Ballast: Electronic 120V or 277V or dual voltage (120V/277V) magnetic. Assembly is accessible from below without tools for inspection and replacement.

12.Junction Box: 0.048" (18-ga.) galvanized steel. UL listed for 8 No. 12 AWG, 90°C through branch circuit conductors; allows inspection from below.

13.Thermal Protector: (not shown) Meets NEC and UL requirements. Do not install insulation above nor within 3" (76mm) of any part of the luminaire.

Electrical

Electronic Ballast: 120V or 277V, 50/60 Hz., encased, high-power factor, T.H.D. <15%, thermally and transient protected, RMI / RFI complies with FCC Part 18 non-consumer equipment, shut-down circuit at end of lamp life, sound rating "A", -5° F minimum starting temperature, Type 1 outdoor rating.

Ballast

ANSI Code

Voltage

Max. Amps

Input Watts

70W MH

M98/M143

120/277

0.67/0.28

78

100W MH

M90/M140

120/277

0.90/0.43

110

Magnetic Ballast: 120V/277V dual voltage, 60 Hz., encased and potted, HX-HPF circuit type, high power factor, sound rating “B”, -20° F minimum

starting temperature, Type 1 Outdoor rating.

 

Ballast

ANSI Code

Voltage

Max. Amps

Input Watts

70W MH

M98/M143

120/277

1.90/0.80

94

100W MH

M90/M140

120/277

2.40/1.10

125

Options and Accessories

Auxiliary: Add suffix A to Frame-In Kit and Reflector Trim. See Spec.Sheet “A/E”

Emergency Lamp: Add suffix E to FIK and Reflector Trim. See Spec.Sheet “A/E”

Slope Ceiling Adapters: See Specification Sheet SCA.

Fuse (magnetic ballast): Add suffix F1 or F2 to FIK (F1=120V F2=277V)

Chicago Plenum: Consult Factory.

Labels

UL (Suitable for Wet Locations), CSA, I.B.E.W.

Job Information

Type:

Job Name:

Cat. No.:

Lamp(s): Notes:

Lightolier a Genlyte companywww.lightolier.com 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish.

© 2005 Genlyte LLC • B0809

Page 1
Image 1
Lightolier C7E17FL-PL specifications Frame-In Kit, Features, Electrical, Options and Accessories, Labels