Electrical (continued from page 1)

Automatic, battery protecting low voltage disconnect (LVD)

Advanced battery diagnostics and management system

Temperature compensated battery charger

24 hour recharge time

High frequency, very low ripple current charger

Input and output disconnect switch

Battery disconnect switch

14.0 kVA Single Phase UPS System

Battery

Maintenance free, sealed lead calcium battery has an estimated service life of 10 years, and an operating temperature range of 65°F (19°C) to 85°F (30°C).

Options

0 = None

1 = PC Format Diagnostics Software

4 = Remote Display + “5”

5 = Additional RS-232

System Input/Output Ratings

SYSTEM

INPUT

INPUT

AVAILABLE OUTPUT VOLTAGES/

 

OCB POLE SPACES

RATING

VOLTAGE

AMPS1

 

MAX. LOAD AMPS2

 

 

AVAILABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

120 V

208 V

240 V

 

277 V

 

 

14,000 VA

277

63.2

116.5

 

50.5

 

12

 

208/240

80.8/70.0

116.5

67.3

58.3

 

 

12

 

 

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1)

Continuous Duty

2) Total Load Not to Exceed System Rating

Warranty

Standard Warranty

Lightolier will provide parts and on-site labor for the first 90 days following shipment of product, and parts only for an additional 270 days.

Extended Warranty

(Available with purchase of Factory Start-Up Service) Lightolier will provide parts and on-site labor for the first 12 months following start-up of the product, and parts only for an additional 12 months.

System One-Line Diagram

Computer Interface Pin Configuration

(AS/400™)

Pin

Description

Function

8

Normal

System Functioning Normally

6

Load On Reserve

Double Conversion Inverter Not Operating

9

Power Failure

Load Supplied by Battery

7

End of Discharge Period Unit Will Soon Stop Operating

5

Common

Common Connection to Above 4 Signals

Listed to

UL 924

Lightolier a Genlyte Thomas Companywww.lightolier.com 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish.

© 2004 Genlyte Thomas Group LLC (Lightolier Division) • D0504