INSTALLATION |
2.Take necessary steps to assure load is limited to the capacity of the Vantage by installing a 50 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 50 amps. Loading above the rated output will reduce output voltage below the allowable
3.Install a 50 amp 120/240 VAC plug (NEMA Type
4.Plug this cable into the 50 Amp 120/240 Volt receptacle on the Vantage case front.
Figure A.2 Connection of the Vantage to Premises Wiring
240Volt
60 Hz.
Service
240 VOLT
POWER
120 VOLT
COMPANY
120 VOLT
METER
GROUNDED CONDUCTOR
NEUTRAL
BUS
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
|
| 50AMP | |
|
| 240 VOLT | |
|
| DOUBLE | |
50 AMP, 120/240 |
| POLE | |
| CIRCUIT | ||
VOLT PLUG | 240 VOLT | ||
BREAKER | |||
NEMA TYPE |
|
|
GND
N
N
LOAD
PREMISES
DISCONNECT AND
SERVICE
GROUNDOVERCURRENT
PROTECTION
50 AMP, 120/240 VOLT
RECEPTACLENOTE: No. 6 COPPER CONDUCTOR CABLE SEE NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
Vantage 500 CUMMINS