OPERATION | ||
|
|
|
ARC GOUGING
The Ranger 250 can be used for limited arc gouging. For optimal performance, set the MODE switch to CC- STICK and the ARC CONTROL to +10.
Set the CONTROL knob to adjust output current to the desired level for the gouging electrode being used according to the ratings in the following table.
Carbon Diameter | Current Range (DC, electrode |
| positive) |
1/8" (3.2mm) | |
5/32" (4.0mm) | |
3/16" (4.0mm) |
AUXILIARY POWER:
Start the engine and set the IDLER control switch to the desired operating mode. Full power is available regardless of the welding control settings providing no welding current is being drawn.
The auxiliary power of the RANGER 250 consists of two 20
The auxiliary power capacity is 9,000 Watts Peak, 8500 Watts Continuous of 60 Hz, single phase power. The auxiliary power capacity rating in watts is equiva- lent to
The 120 V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs. The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.
NOTE: The 240 V receptacle has two circuits, each of which measure 120 V to neutral but are of opposite polarities and cannot be paralleled.
Simultaneous Welding and Auxiliary Power Loads The above auxiliary power ratings are with no welding load. Simultaneous welding and power loads are specified in the following table. The permissible cur- rents shown assume that current is being drawn from either the 120 VAC or 240 VAC supply (not both at the same time).
Ranger 250 Simultaneous Welding and Power Loads |
| |||
|
|
|
| |
|
|
|
| |
Welding | Permissible | Permissible | Auxiliary | |
(Unity Power Factor) | Current in | |||
|
|
|
|
|
|
| @120 VAC * |
| @ 240 VAC |
0 | 8500 | 70** |
| 35 |
100 | 6200 | 52** |
| 26 |
150 | 4800 | 40** |
| 20 |
200 | 3400 | 28 |
| 14 |
250 | 2000 | 16 |
| 8 |
|
|
|
|
|
*Each duplex receptacle is limited to 20 amps.
**Not to exceed 35 A per 120 VAC branch circuit when splitting the 240 VAC output.
Ranger 250 Extension Cord Length Recommendations
(Use the shortest length extension cord possible sized per the following table.)
Current Voltage | Load |
|
| Maximum Allowable Cord Length in ft. (m) for Conductor Size |
|
| ||||||||
(Amps) | Volts | (Watts) | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG | ||||||
15 | 120 | 1800 | 30 | (9) | 40 | (12) | 75 | (23) | 125 | (38) | 175 | (53) | 300 | (91) |
20 | 120 | 2400 |
|
| 30 | (9) | 50 | (15) | 88 | (27) | 138 | (42) | 225 | (69) |
15 | 240 | 3600 | 60 | (18) | 75 | (23) | 150 | (46) | 225 | (69) | 350 | (107) | 600 | (183) |
20 | 240 | 4800 |
|
| 60 | (18) | 100 | (30) | 175 | (53) | 275 | (84) | 450 | (137) |
35 | 240 | 8500 |
|
|
|
| 60 | (18) | 100 | (30) | 175 | (53) | 250 | (76) |
|
|
|
| Conductor size is based on maximum 2.0% voltage drop. |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RANGER 250