PAGE 6

BIASI B/40

 

 

2. General Information:

The Linear series are wet base design, sectional, cast-iron boilers for forced hot water heating systems. The Linear boilers are designed for firing with oil and deliver high efficiencies through unique design and construction.

The Linear series boilers are shipped from the factory in assembled blocks and each boiler can range from 6 to 12 sections. The sections can then be disassembled before delivery to the jobsite by QHT and then field assembled. The boiler jacket, burner and controls are packed separately for shipping.

Note: All equipment should be inspected upon delivery, and any damage or shortage should be reported immediately.

Boiler

 

 

Input

Input

 

 

Water

 

 

Model

Number of

Heating

Oil

Gas

Net Output

 

Content

Length

Weight

Number

Sections

Capacity

G.P.H.

MBH

MBH

Efficiency %

Gals.

(L) inches

(LBS)

B40/6

6

265

2.20

308

230

86.0

17

34.8

902

B40/7

7

352

2.90

406

305

86.7

20

39.5

1023

B40/8

8

437

3.60

504

380

86.8

23

44.4

1144

B40/9

9

524

4.30

602

456

87.0

26

49.2

1265

B40/10

10

610

5.00

700

532

87.2

28

53.9

1386

B40/11

11

696

5.70

798

607

87.2

31

58.8

1507

B40/12

12

783

6.40

896

684

87.4

34

63.8

1628

 

 

 

 

 

 

 

 

 

 

MaximumWater Working Pressure 72 psi

 

MaximumRelief Valve is 50 psi @ 900 MBH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. Conforming to Codes and Regulations:

Installation of the boiler, burner, oil tank and related equipment must conform to national, state and local regulating agencies and codes applicable to the installation of the equipment. In the absence of local requirements, the following codes apply:

ANSI/NFPA - #31 Installation of Oil Burning Equipment

ANSI/NFPA - #70 National Electric Code

ANSI/NFPA - #211 Chimneys and Vents

The above codes are available from:

National Fire Protection Association (NFPA)

Battery March Park

Quincy, Massachusetts, 02269

Page 6
Image 6
Linear Boiler installation instructions General Information, Conforming to Codes and Regulations, Weight