
First, review the Offset Elevation Chart and Figure 40 for reference.
Step 1. Determine the offset distance where chimney is to pass through the first ceiling- dimension “A.” To find this point on your ceil- ing, first determine the center point for a vertical chimney following the instructions for vertical installation.
Measure height to the ceiling from the top of
Step 2. Proceed by using the Straight Up Installation Instructions for cutting and framing ceiling and roof openings.
Note: See Framing and Dimension Chart for the sizes of the ceiling and roof openings. The size of the roof opening varies with the degree of pitch of the roof.
Offset Elbow AssemblyOffset elbows install the same as chimney sections. First, snap the inner section INTO the preceding inner section of flue. Check connection by pulling up slightly to ensure a tight fit. Next, the outer sections snap lock OVER the preceding outer section of chimney. Again, check outer section by pulling up slightly to ensure proper connection is made.
Return Elbow AssemblyReturn elbows install the same way as round terminations and stabilizers:
Step 1. Hold return elbow over top of last chimney section.
Step 2. Center inner slip section into inner flue
Step 3. Center
Step 4. Pull up slightly on return elbow to ensure locking joint has firmly engaged.
Step 5. Secure support straps to framing members by nailing under tension in sheer (Figure 41 ).
14
Return
Elbow
Figure 41
Note: The return elbow assembly performs the same function as a stabilizer. Consider this when determining the need for a stabilizer.
Note: Do not apply excessive pressure to any subsequent chimney section following return elbow assembly when installing. Ensure that each subsequent chimney section is securely attached by testing as noted above.
CHIMNEY 30° OFFSET THROUGH FLOOR
OR CEILINGIt may be necessary to assemble the chimney at 30° when passing through the floor or ceiling area. Use the
Attic Space |
| |
2" Min. | ||
Firestop Spacer | ||
| Air Space | |
2" Min. | ||
Stabilizer | ||
Air Space | ||
| ||
10' |
| |
Max. | 30° Firestop | |
| And Attic Above | |
Figure 42 |
| |
Room Above |
| |
2" Min. | ||
Firestop Spacer | ||
| Air Space | |
2" Min. | ||
Air Space | Stabilizer | |
10' | 30° Firestop | |
Max. | And Room Above |
Figure 43
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Use combustion air kit, Model
Outside air drawn into the fireplace supplies air to the fire for combustion. Only one combustion air duct on the left side of the fireplace is necessary if installed (Figure 44 ).
Provision for
Outside Air
Figure 44
If additional length of duct is necessary, purchase locally available U.L. Class 0 or Class 1 metallic duct. The duct may extend up to 50' (15.24 m) in any direction.
Note: When installing the air duct vertically, DO NOT terminate the duct closer than 3' (914mm) below the chimney top.
There is a
CAUTION: NEVER LOCATE INLET WHERE IT CAN BE BLOCKED BY SHRUBS, SNOW DRIFTS, ETC. NEVER LOCATE INLET IN GARAGE OR ANY AREA WHERE THERE IS ANOTHER