Status display screens

User’s Information Manual

3SMART SYSTEM control module (continued)

Status display screens

Status Display Screens

By using the Previous/Next (￿, ￿) arrow keys on the SMART SYSTEM display panel, you can navigate through the nine (9) display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:

Screen

Display shows:

Description

 

HTR: OFF

The unit has been turned OFF by the Enter/Reset button on the

 

SMART SYSTEM display panel.

 

 

 

 

 

 

Standby

The unit has not received a call for heat from a remote thermostat nor

 

has it received a call for heat from a DHW thermostat.

 

 

 

 

 

 

Set Point Met

The unit has met the water temperature set point, but is still receiving

 

a call for heat from either a remote thermostat or a DHW thermostat.

 

 

 

 

 

 

Prepurge

The unit has initiated the 10 second purge and 15 second HSI warm-

 

up periods on a call for heat.

 

 

 

Ignition

The unit has begun a 5 second trial for ignition.

 

 

 

 

SH***% Rate

The unit has fired and is running at the displayed percentage.

 

DHW***% Rate

 

 

#1

 

 

 

The call for heat has been satisfied and the unit runs the fan for an

 

Postpurge

additional 10 seconds to clear the combustion chamber and vent

 

 

system of residual flue products.

 

 

 

 

Service

The unit has been placed in a temporary mode that will allow the unit

 

to fire for the purpose of combustion analysis.

 

 

 

 

 

 

 

When the outlet sensor has been selected as the control sensor

 

OUT: ***F(***)

(default), the control will display the outlet temperature as well as the

 

 

set point in parenthesis.

 

 

 

 

 

If the outlet sensor has not been selected as the control sensor or a

 

***F

system supply sensor is connected, only the outlet temperature will be

 

 

displayed.

 

 

 

 

Open

The control does not detect the outlet sensor.

 

 

 

 

Shorted

The outlet sensor wires or the sensor itself has become shorted.

Press the Next ￿ arrow key on the SMART SYSTEM display to access Screen #2.

 

 

If the inlet sensor has not been selected as the control sensor or a

 

IN: ***F

system return sensor is installed, only the inlet temperature will be

 

 

displayed.

 

 

 

 

 

When the inlet sensor has been selected as the control sensor, the

 

***F (***)

control will display the inlet temperature as well as the set point in

#2

 

parenthesis.

 

Open

The control does not detect the inlet sensor.

 

 

 

 

Shorted

The inlet sensor wires or the sensor itself has become shorted.

 

 

 

 

RISE: ***F

The difference between the inlet temperature and the outlet

 

temperature.

 

 

Press the Next ￿ arrow key on the SMART SYSTEM display to access Screen #3.

Status Display Screens 13 Screen

Page 13
Image 13
Lochinvar 1501, 502 Status display screens, Status Display Screens, Display shows, Description, User’s Information Manual

FAQ

How many display screens are there?

There are nine display screens that you can navigate through using the Previous/Next arrow keys on the SMART SYSTEM display panel.

What does 'Standby' status indicate?

The unit has not received a call for heat from a remote thermostat nor has it received a call for heat from a DHW thermostat.

What does the 'Open' status for inlet sensor mean?

It indicates that the control does not detect the inlet sensor.