Figure 13_1 1/2" - Flow vs. Pressure Drop
FLOW vs. PRESSURE DROP
Pressure Drop, PSID
FLOW IN U.S. GPM
Figure 15_2 1/2" - Flow vs. Pressure Drop
Figure 14_2" - Flow vs. Pressure Drop
Maintenance instructions
The LTV valve is maintenance free. It does not require regular cleaning or calibration. In most installations, the
If the valve becomes unable to maintain a consistent inlet water temperature of 125°F during steady state firing conditions, replace the valve or the wax element inside the valve.
WARNING The recommended maximum high temperature to the valve should be 175°F; the
absolute maximum is 195°F.