Lochinvar 673 1 Copper-Fin Boiler Dimensions & Specifications, Standard Features, Venting, Input

Models: 455 36 92-1/2 33-1/2 15-3/4 11 11 33-3/4 2 14 1350 CBN2067 2065 81% 1 CBN1437 1435 81% 1 162 1 264 36 82-1/4 33-1/2 15-3/4 11 11 33-3/4 2 14 1193 454 1 010 36 68-3/4 33-1/2 15-3/4 10-1/2 10-1/2 33-3/4 2 12 1050 673 1 CBN1257 1255 81% 1 CBN0647 645 81% 522 454 31-1/2 56-3/4 22-1/4 12-1/2 9-1/2 28-1/2 29-1/2 1-1/4 8 510 CBN0497 495 81% 401 349 31-1/2 45-1/4 22-1/4 12-1/2 9-1/2 22-3/4 29-1/2 1-1/4 6 440 017 884 36 58-1/2 33-1/2 15-3/4 9-1/2 10-1/2 33-3/4 2 12 905 CBN0747 745 81% 603 524 31-1/2 64 22-1/4 12-1/2 9-1/2 32 29-1/2 1-1/4 8 550 CBN1797 1795 81% 1

1 2
Download 2 pages 47.22 Kb
Page 2
Image 2
Copper-Fin®Boiler Dimensions & Specifications

Copper-Fin®Boiler Dimensions & Specifications

Copper-Fin Heating Boiler

 

 

 

Dimensions & Specifications

 

 

 

 

Input

 

Heating

Net

 

 

 

 

 

 

 

 

 

 

Model

Max

Thermal Capacity I=B=R

 

 

 

 

 

 

 

Gas

Vent

Shipping

Number MBH Efficiency

MBH

MBH

A

B

C

D

E

F

G

Conn.

Size

Weight

CBN0497

495

81%

401

349

31-1/2”

45-1/4”

22-1/4”

12-1/2” 9-1/2”

22-3/4” 29-1/2”

1-1/4”

6”

440

CBN0647

645

81%

522

454

31-1/2”

56-3/4”

22-1/4”

12-1/2” 9-1/2”

28-1/2” 29-1/2”

1-1/4”

8”

510

CBN0747

745

81%

603

524

31-1/2”

64”

22-1/4”

12-1/2” 9-1/2”

32”

29-1/2”

1-1/4”

8”

550

CBN0987

985

81%

798

694

36”

48-1/4”

33-1/2”

15-3/4” 8-1/2”

8-1/2” 33-3/4”

2”

10”

845

CBN1257

1255

81%

1,017

884

36”

58-1/2”

33-1/2”

15-3/4” 9-1/2”

10-1/2” 33-3/4”

2”

12”

905

CBN1437

1435

81%

1,162

1,010

36”

68-3/4”

33-1/2”

15-3/4” 10-1/2”

10-1/2” 33-3/4”

2”

12”

1050

CBN1797

1795

81%

1,454

1,264

36”

82-1/4”

33-1/2”

15-3/4”

11”

11”

33-3/4”

2”

14”

1193

CBN2067

2065

81%

1,673

1,455

36”

92-1/2”

33-1/2”

15-3/4”

11”

11”

33-3/4”

2”

14”

1350

Notes: Change ‘N’ to ‘L’ for LP gas models. No deration on LP models.

Performance data based on manufacturer test results.

Water connections for models CB 0497-747 are 2” NPT on 6-1/2” centers. Water connections for models CB 0987-2067 are 2-1/2” NPT on 11-1/4” centers.

Standard Features

81% Thermal Efficiency

Flow Switch

Electronic Temperature Control

24 Volt Control System

Fan Assisted Combustion

BMS Terminal Strip

Sealed Combustion Chamber

Combustion Air Filter

Stainless Steel Burners

Freeze Protection

Low NOx Operation Exceeds the most

10 Year Limited Warranty on Heat

Stringent Air Quality Requirements

Exchanger (See warranty for details)

ASME Copper Finned Tube

Optional Equipment

Heat Exchanger

160 psi Working Pressure

Alarm Bell

Gasketless Heat Exchanger Design

Contacts on any Failure

Pump Relay w/ Delay

Contacts for Air Louvers

Down Stream Test Valve

Cupro-Nickel Heat Exchanger

Referenced Gas Valves

High & Low Gas Pressure Switch

Loch-Heat Ceramic Tile

w/ Manual Reset

Combustion Chamber

Outdoor Reset Control

Hot Surface Ignition

Manual Reset Low Water Cut-Off

Adjustable High Limit w/ Manual Reset

w/ test

ASME Pressure Relief Valve

Stack Frame

Temperature & Pressure Gauge

MP2 Sequencer

Available Firing Systems

M9 Hot Surface Ignition with Electronic Supervision (Standard)

M13 GE GAP/FM/CSD1

M7 California Code

Venting

Outdoor Vent Cap

Registered under U.S. Patent # 5,989,020

For Ease In Ordering

By Model Number

C B

N

0 4 9 7

M 9

 

 

.

 

FIRING

 

 

 

 

This boiler is a 495,000 Btu/hr,

natural gas Copper-Fin. It has M9 firing controls

Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000

www.Lochinvar.com

CBN-07(Replaced CBN-06 3/10)

FG-10M-5/11-Printed in U.S.A.

Page 2
Image 2
Lochinvar 673 1 Copper-Fin Boiler Dimensions & Specifications, Standard Features, Optional Equipment, Venting, Input, Conn