2Pre-installation

1.The installation must conform to the instructions in this manual and all applicable local, state, provincial, and national codes, laws, regulations, and ordinances. Installations in Canada must conform to B149.2 Installation Code.

2.Be certain the domestic water supply to the tank has physical and chemical characteristics that fall within the limits shown in Table 2A. Where questions exist as to the composition of the water on the job, a qualified water treatment expert should be consulted.

CAUTION

Water with characteristics outside the

limits shown in Table 2A may severely

 

 

shorten the life of the tank due to

 

corrosion. Damage to tanks in such

 

cases is not covered under warranty.

3.Read and understand all installation requirements in this manual.

Table 2A

Water Chemistry Requirements

Water used in the tank must have characteristics falling within the following limits:

 

Characteristic

Min.

Max.

 

 

 

 

 

Ph

6.0

8.0

 

 

 

 

 

Chloride (PPM)

--

80

 

 

 

 

 

 

 

 

Figure 2-1Element Cover Clearances

24” MIN CLEARANCE FROM

ELEMENT COVER

(SET Models)

SDT/SET Installation & Operation Manual

Locating the Tank

1.Choose a location for your water heater centralized to the piping system. You must also locate the SDT/SET water heater where it will not be exposed to freezing temperatures. Additionally, you will need to place the water heater so that the controls, drain, and inlet/outlets are easily accessible.

This appliance must not be installed outdoors, as it is certified as an indoor appliance, and must also be kept vertical on a level surface.

2.Keep distance between boiler and water heater to a minimum to:

a.reduce piping heat loss

b.provide minimal friction loss

3.Figure 1-1 on page 4 shows the weights of all the tanks filled with water. Make sure that the location chosen for the tank is capable of supporting it.

CAUTION

This appliance must be placed where leakage

from the relief valve, leakage from the related

 

 

piping, or leakage from the tank or

 

connections, will not result in damage to the

 

surrounding areas, or to the lower floors of

 

the building. A water heater should always be

 

located in an area with a floor drain or

 

installed in a drain pan suitable for water

 

heaters. Lochinvar shall not be held liable for

 

any such water damage.

4.The tank may be located some distance from the boiler provided the pump is designed to provide the flow called for in Table 3B (page 7)- Pressure Drop Values, through the coil. The further the tank is from the boiler, the longer the response of the boiler will be to a call from the tank zone. Insulate piping between the boiler and the tank.

￿WARNING Failure to properly support the tank could result in property damage or personal injury.

Recommended Clearances

The installation location must provide adequate clearances for servicing and proper operation of the water heater. A 12 inch vertical clearance is recommended from the top of the water heater. A zero clearance is allowed for the sides of the water heater. However, boiler, electrical, and servicing clearances must be figured when locating the water heater.

Minimum Clearance to the Element Cover

See FIG 2-1. Clearances must be a minimum of 24-inches to allow for element removal and replacement on SET model.

5

Page 5
Image 5
Lochinvar SDT/SET065 - 119 Pre-installation, Minimum Clearance to the Element Cover, Characteristic Min Max

SDT/SET065 - 119 specifications

The Lochinvar SDT/SET065 - 119 is a sophisticated heating solution that combines efficiency, reliability, and innovative technology to meet the demands of modern residential and commercial applications. As a participant in the highly competitive heating market, Lochinvar has established a reputation for producing high-quality products, and the SDT/SET065 - 119 is no exception.

One of the main features of the Lochinvar SDT/SET065 - 119 is its high-efficiency operation. With an impressive thermal efficiency rating, this unit minimizes energy consumption while maximizing output. This efficiency not only helps in reducing utility bills for users but also contributes to a more sustainable environment by lowering carbon emissions. The design of the unit incorporates advanced heat exchanger technology that optimizes thermal transfer, ensuring that homeowners and businesses receive the precise heating they require.

The SDT/SET065 - 119 also boasts impressive versatility. It can be configured to work with various hydronic heating systems, making it suitable for a wide range of applications, from radiant floor heating to baseboard heating systems. Additionally, the compact design of the unit allows for easy installation and integration into existing systems, without requiring significant modifications.

User-friendly controls are another highlight of the Lochinvar SDT/SET065 - 119. The unit features advanced digital control technology that allows for easy temperature regulation and monitoring. This technology also enables users to take advantage of multiple operating modes, enhancing both comfort and efficiency. Furthermore, built-in diagnostic capabilities provide real-time feedback on the system’s performance, facilitating easier troubleshooting and maintenance.

Safety is also a key consideration in the design of the SDT/SET065 - 119. The unit includes multiple safety features, such as over-temperature protection and pressure relief systems, ensuring reliable operation without compromising user safety.

In summary, the Lochinvar SDT/SET065 - 119 exemplifies modern heating technology. Its high efficiency, versatility, user-friendly controls, and robust safety features make it an ideal choice for those seeking a reliable and effective heating solution. Whether for residential or commercial use, the Lochinvar SDT/SET065 - 119 stands out as a top-tier option in the heating market.