User’s Information Manual
2 Maintenance schedule (continued)
The condensate trap (FIG.
boiler operation to avoid flue gas emission from the condensate drain line. Failure to ensure the float ball is in place could result in severe personal injury or death.
Clean/Inspect Trap Assembly
1.Remove the clean out cap on the bottom of the trap. Let the condensate and any debris drain out.
2.Refill the trap according to the instructions on page 6.
Figure 2-1 Condensate Trap
COMPRESSION
FITTING
FLOAT BALL
CONDENSATE
DRAIN
REMOVABLE CAP TO
CLEAN OUT TRAP
NOTICE | Use materials approved by the authority | |
having jurisdiction. In the absence of | ||
| ||
| other authority, PVC and CPVC pipe | |
| must comply with ASTM D1785 or D2845. | |
| Cement and primer must comply with | |
| ASME D2564 or F493. For Canada use | |
| CSA or ULC certified PVC or CPVC pipe, | |
| fittings, and cement. | |
| To allow for proper drainage on large | |
NOTICE | ||
horizontal runs, a second line vent may | ||
| be required and tubing size may need to | |
| increase to 1 inch. |
The condensate line must remain unobstructed, allowing free flow of condensate. If condensate is allowed to freeze in the line or if the line is obstructed in any other manner, condensate can exit from the boiler tee, resulting in potential water damage to property. Call your qualified service technician to inspect the boiler and system.
6.A condensate removal pump is required if the boiler is below the drain. When installing a condensate pump, select one approved for use with condensing boilers and furnaces. The pump should have an overflow switch to prevent property damage from condensate spillage. Call your qualified service technician to inspect the boiler and system.
Figure 2-2 Condensate Disposal
Condensate disposal
1.This boiler is a high efficiency appliance that produces condensate.
2.The bottom of the boiler has a 1 1/4 inch pipe for connection of the condensate trap (FIG.
3.Slope condensate tubing down and away from the boiler into a drain or condensate neutralizing filter. Condensate from the Knight wall mount boiler will be slightly acidic (typically with a pH from 3 to 5). Install a neutralizing filter if required by local codes.
A Neutralizer Kit is available from the factory (Kit 3087).
4.Do not expose condensate line to freezing temperatures.
5.Use only plastic tubing or piping as a condensate drain line (FIG.
CONDENSATE
TRAP
REMOVABLE CAP
FOR CLEANING TRAP
SECURE INTO
CONDENSATE DRAIN
STAND PIPE
CONDENSATE DRAIN
STAND PIPE
CONDENSATE DRAIN CONNECTION - ROUTE TO FLOOR DRAIN OR NEUTRALIZING FILTER USING
3/4" CORRUGATED TUBING
7