Lopi Stove Installation for qualified installers only, Hearth Stove Positive Connection

Models: Stove

1 40
Download 40 pages 32.54 Kb
Page 17
Image 17
Hearth Stove

Stove Installation (for qualified installers only)

17

Hearth Stove

Positive

Connection

NOTE:

Most factory-built chimney manufacturers make stainless steel chimney liners, either flexible or rigid. This provides a wide variety of installation options. Make sure to follow the manufacturer's instructions for installation and support

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cap and flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

prevents water from

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: The entire fireplace and

 

 

 

 

 

 

 

 

 

 

 

 

entering

 

 

 

 

chimney must be clean, undamaged,

 

 

 

 

 

 

 

 

 

 

 

 

 

and meet all local building codes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(UBC, etc.). Damage must be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

repaired prior to installation. The

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

chimney must be 15' to 33' tall.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The liner must be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

stainless steel connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or flexible vent. Follow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the liner manufacturer's

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

instructions for installation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Combustible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and support.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mantle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min. 36"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airtight Insulated

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Clean-Out

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remove damper

Floor Protection

or wire it open

 

(See the section

 

"Floor Protection

See the section

Requirements"

"Stove Placement

for more details)

Requirements" for

 

minimum clearances

 

required.

Figure 15

Hearth Stove Direct Connection

NOTE:

Direct connections require installation of an airtight, non-combustible block-off plate or damper adapter.

NOTE: The chimney must have a clay tile liner. If it does not, the installation must use a positive connection (full reline). The entire fireplace and chimney must be clean, undamaged, and meet all local building codes (UBC, etc.). Damage must be repaired prior to installation. The chimney must be 15' to 33' tall.

Combustible Mantle

Min. 36"

Floor Protection

(See the section "Floor Protection Requirements"Hearth Stove Direct Connection for more details)

Clay

Liner

Stainless steel chimney connector must Extend 1' past the block-off plate or to the flue liner

Airtight

Insulated

Clean-Out

Remove damper or wire it open

Block-off plate or damper adapter

See the section "Stove Placement Requirements" for minimum clearances required.

Figure 16

© Travis Industries

100-01177

4060802

Page 17
Image 17