Thermal Max Detector
4351E
•Addressable conventional technology
•Alarm temperature 78°C
•Addressing by means of address module or detector parameterisation
•Remote readout of detector condition
•Function testable with Remote Test Unit ECO1000RTU
Description
The Thermal Max Detector 4351E recognises a maxi- mum temperature of 78°C as sign of fi re. It complies with Class BS and can be used up to a room height of 6m.
Addressable conventional technology is used for alarm transmission to the fi re detection control panel. The detector addressing can be achieved in 2 ways:
•A detector with an Address Module
•An address, which has been stored in the detector by means of the Remote Programming and Test Unit,
is displayed on the Zonal Display Unit S300ZDU.
A test activation of the detector can be carried out using the Remote Test Unit ECO1000RTU. In addition to the test activation of the detector, the Remote Pro- gramming and Test Unit S300RPTU can also be used to set and display the following detector parameters:
•the detector address, and
•the date of the previous maintenance.
The detector can be attached to various detector ba- ses and it can be protected against theft.
Specifications
Operating voltage | Supply through the detector line voltage |
Current consumption | typ. 85µA (quiescent) |
Alarm temperature | 78°C |
Ambient temperature | |
Relative humidity | 5 – 95% (no condensation) |
Dimensions ø × H | 102 × 43 (mm) |
Colour | cream |
Weight | 75g |
Approval | VdS G202016 |
Order number | 242041 |
Order name | Thermal Max Detector/Conv./300/SS 4351E |
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • | 4351E_DBL_LST_EN_0804.PDF • PAGE 1 |
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED |
|