LST 5251EM manual Description, Building Safety. Building Security, Thermal Detector

Models: 5251EM

1 2
Download 2 pages 38.53 Kb
Page 1
Image 1
Thermal Detector

Thermal Detector

5251EM

ADM loop technology with System Sensor/200 protocol

For use as maximum heat or rate-of-rise heat detector

Alarm temperature 58°C or 78°C software selectable
Optional connection of remote indicator
Function testable with magnet

Description

The addressable Thermal Detector 5251EM is based on the heat principle and was developed for the indoor temperature supervision in a wide range of fi re detec- tion applications.

When used with a Fire Detection Control Panel Series BC216, the detector can operate either as maximum heat detector with alarm temperature 58°C (EN 54-5 Class A1S) or alarm temperature 78°C (EN 54-5 Class BS), or as rate-of-rise heat detector with a maximum temperature of 58°C (EN 54-5 Class A1R).

The proven ADM loop technology with System Sen- sor/200 protocol establishes a permanent communi-

cation between the fi re detection control panel and the detector. That ensures a periodical function testing of the detector. Fires are safely detected in the control panel by continuously analysing the measured values.

The two LEDs with 360° visibility indicate the activated condition of the detector. The detector address is se- lected with two decadic rotary switches, thus allowing to change the detector without additional tools.

A detector function test can be conveniently conducted using a magnet or a detector test device. The detector can be attached to various bases and it can be protec- ted against theft.

Building Safety. Building Security.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27

5251EM_DBL_LST_EN_0804.PDF • PAGE 1

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 

Page 1
Image 1
LST 5251EM manual Description, Building Safety. Building Security, Thermal Detector, •Function testable with magnet