LST 5251EM manual Specifications, Building Safety. Building Security

Models: 5251EM

1 2
Download 2 pages 38.53 Kb
Page 2
Image 2
Specifications

Specifications

Operating voltage

Supply through loop voltage

Current consumption

max. 200µA (quiescent)

Alarm temperature

 

Class A1S

typ. 58°C (maximum principle), max. room height 7.5m

Class A1R

typ. 58°C (rate-of-rise principle), max. room height 7.5m

Class BS

typ. 78°C (maximum principle), max. room height 6m

Operating temperature

 

Classes A1S and A1R

max. +45°C

Class BS

max. +68°C

Ambient temperature

-20°C to +60°C (continuous operation)

Relative humidity

10 – 93% (no condensation)

Dimensions ø × H

102 × 51 (mm)

Colour

cream

Weight

102g

Approval

VdS G200094

Order number

242002

Order name

Thermal Detector/Anal./200/SS 5251EM

Building Safety. Building Security.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27

5251EM_DBL_LST_EN_0804.PDF • PAGE 2