LST BCnet216: 19 manual Permanent Connection, Network Expansion of BC216-1CE, Specifications

Models: BCnet216: 19

1 5
Download 5 pages 33.54 Kb
Page 4
Image 4
Permanent Connection

Permanent Connection

A variety of peripheral devices can be connected to the fi re detection control panel Series BC216-1CE and to the BCnet sectional control panel BC216-3CE:

• Fire brigade key safe

• Transmitting device for the actuation of pagers via

• Fire brigade control unit

ESPA protocol

• Acoustic and optical signaling devices

• Modules for remote parameterisation and remote

• External protocol printer

maintenance via computer newtork, modem or GSM

• Remote display and operating panels

connection

• Remote indication unit

• Transmitter module for the transmission of messages

• Actuations

via SMS or e-mail

• Electronic monitoring system

– and much more.

Network Expansion of BC216-1CE

By installing a Network Interface Module NIF5-1M in the Fire Detection Control Panel BC216-1CE, the latter can be integrated as BCnet sectional control panel with dis- play and operating fi eld into a Fire Detection Control

Panel BCnet216. All sectional control panels are con- nected with each other via a redundant high-security network (the Global Security System network GSSnet).

Extinguishing Control System

If required, the BC216-1CE or the BCnet216 can be easily expanded to an extinguishing control panel ac- cording to EN 12094-1. The extinguishing control panel LC216-1 controls up to 8 fl ooding zones in one extin- guishing system, without hardware redundancy. The networked extinguishing control panel LCnet216 can control up to 127 fl ooding zones in a maximum of 127 extinguishing systems.

The function of the extinguishing control panel is fully

integrated into the fi re detection control panels Series BC216, a combined operation is therefore possible. The LC216-1 and LCnet216 are certifi ed to EN 54-2, EN 54-4, EN 12094-1 and VdS as a pure extinguishing control panel and as a combined fi re detection and ex- tinguishing control panel.

The networked extinguishing control panel LCnet216 can be optionally implemented with full hardware red- undancy.

Specifications

Mains voltage

230VAC +10/-15%, 50Hz

Connection power

60VA

Output voltage

typ. 28VDC

Output peak current

max. 1.8A

Connection of external devices

typ. 0.8A, site-specifi c

Own current consumption at 24V

typ. 90mA (without optional componentries)

Ambient temperature

-5°C to +50°C

Dimensions W × H × D

478 × 266 (6 height units) × 95 (mm)

Colour

gray-white, RAL 9002

Weight without accumulator

approx. 6kg

Approvals (EN 54-2, EN 54-4)

VdS G201017

 

FT 14/147/3/99 (Austria)

Building Safety. Building Security.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27

BC216CE_DBL_LST_EN_0804.PDF • PAGE 4

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 

Page 4
Image 4
LST BCnet216: 19 manual Permanent Connection, Network Expansion of BC216-1CE, Extinguishing Control System, Specifications