Clear Concept

The compact control panel BC216-1CE and the BCnet sectional control panel BC216-3CE are modularly desi- gned control panels in 19“ slide-in technology. Depen- ding on their confi guration, they provide the following features:

The Conventional Detector Interface GIF8-1 permits the connection of automatic detectors and manual call points in conventional technology as well as spe- cial detectors with contact output. Individual detector identifi cation can be achieved by means of an optio- nal address module.

Detectors and modules in ADM loop technology can be connected to the Loop Interface LIF64-1. Depen- ding on the parameterisation, either the Apollo/Disco- very protocol or the System Sensor/200 protocol is used to achieve bi-directional data transfer.

Since the BCnet216 is compatible to LST fi re detec- tion control panels of previous generations, the ex- change or expansion of existing systems in conventi- onal technology or ADM loop technology is possible. The existing detector installation can be used without changes.

The optional Fire Brigade Interface FWI2-1 serves for the connection of two independent transmitting devices for a direct interconnection to a designated alarm respondent (e.g., the fi re brigade) as well as for the connection of a country-specifi c fi re brigade control unit. By using the Fire Brigade Interface Addi- tional Board FWZ2-1, a line supervision for both of the transmitting devices is accomplished.

Customizable outputs and logical combinations of detectors and detector zones for the activation of external controls and alarming devices facilitate ma- ximum fl exibility. Thus, no additional expenses arise for external relays, logic gates or timers. Thanks to the wide range of parameterisation possibilities, indi- vidual requirements even under the most diffi cult am- bient conditions can be combined into a reasonable fi re protection strategy.

A monitored siren output and dry relay contacts for alarm and fault are available by default.

By integrating input and output modules on any positi- on in the loop you can realize enablements or disable- ments as well as control tasks in your system without having to care for additional wires.

The free combination of detectors and modules into logic sectors allows for the joint operation of defi ned parts of the system even beyond the limits of loops or sectional control panels.

The use of unshielded loop cables allows for cost- saving and uncomplicated installation as well as for the possibility of reusing the existing cabling.

The LC text display (BC216-1CE) shows events with the full information such as fl oor, room identifi cation as well as date and time. This allows for quick and targeted reaction in the event of a fi re as well as for easy maintenance.

An event memory allows for the display of the latest 500 events at any time (in the BCnet216 on the main operating unit) with all required information. Thus, all system conditions and user operations that occurred are documented in a clearly laid out way.

At a central processing board failure, the diversifi ed redundancy concept ensures secure alarm recogniti- on.

The processor-monitored power supply ensures per- manent surveillance and charging of the batteries. This way, even during a mains power failure the un- troubled and uninterrupted operation (for more than 72 hours depending on the design) is guaranteed.

Three hierarchized authorization levels for operation and parameterisation facilitate a high degree of secu- rity against unauthorized access.

The BC216-1CE control panel is easily operated menu-driven via the display and operating fi eld. Clear instructions on the display guide the user during com- missioning, operation and maintenance.

The parameter data of the BC216-1CE can be en- tered either via the display and operating fi eld or, in a more comfortable way, can be created by means of PC software PARSOFT and loaded into the cont- rol panel. The parameters of a BC216-3CE sectional control panel are categorically set by means of PC software PARSOFT. Thus, a quick and effi cient trans- fer of the system confi guration into the control panel is guaranteed.

AUTO setup facilitates parameterisation when the control panel is commissioned or expanded and thus helps to save time.

The fl at case allows for easy mounting in virtually all 19“ pivoting frames, racks and housings. The case can accommodate the function modules and the auxiliary modules, apart from the central processing board. The batteries can be placed either into the cabinet rack or (up to 22Ah) into the optional battery bracket. Series BC216 thus stands for modularity and easy expansion.

These products comply with all relevant standards of EN 54 and are VdS-certifi ed. In addition, the products also hold several country-specifi c approvals and certi-

cates. LST‘s high quality level is secured by a perma- nently monitored quality management system certifi ed by ISO 9001.

Building Safety. Building Security.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27

BC216CE_DBL_LST_EN_0804.PDF • PAGE 2

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 

Page 2
Image 2
LST BCnet216: 19 manual Clear Concept