Thermal ROR Detector
HT-11001
•Addressable conventional technology
•Maximum temperature 57°C
•Individual detector addressing by means of optional address module
•Optional connection of remote indicator
•Extremely flat design
•Sealed electronics
Description
The Thermal ROR Detector
fires. The detector complies with Class A1R and can be used up to a room height of 7.5m.
Addressable conventional technology is used for alarm transmission to the fi re detection control panel. By
means of the optional Address Module
A detector fault is indicated by a yellow fl ashing of the multicoloured status LED.
The detector can be attached to various bases and it can be protected against theft.
Specifications
Operating voltage | Supply through the detector line voltage |
Current consumption | typ. 65µA (quiescent) |
Alarm temperature | 57°C |
Operating temperature | max. +50°C |
Ambient temperature | - 40°C to +70°C (no condensation or icing) |
Relative humidity | 0 – 98% (no condensation) |
Dimensions ø × H | 100 × 36 (mm) |
Colour | white |
Weight | 70g |
Approval | VdS G204033 |
Order number | 242030 |
Order name | Thermal ROR Detector/Conv./ORBIS/Apo |
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • | |
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED |
|