Address Module
NG58-1
•Allows to address conventional detectors Series FC600, 100, 300 and ECO1000
•Indication of detector number and assigned element text on suitable fire detection control panels
•Output for optional remote indicator
•Extremely small design
•Installation in the detector base
Description
The Address Module
The address module is installed in the detector base and is preset with the detector address (within the num- ber range 0 – 63) by cutting wire jumpers. In case of alarm, the unique identifi cation of the activated conven- tional detector is achieved by transmitting the address
to the fi re detection control panel.
Apart from the detector address, on Fire Detection Control Panels BC216 a possibly parameterised ele- ment text (for example with the name of the room or fl oor) can also be displayed.
In addition to individual addressing, the address mo- dule can as well be used for addressing a group of several detectors. Thus, in case of alarm activation, the address module achieves a summary indication of this detector group.
Specifications
Current consumption at 24 V | 18mA (active) |
Ambient temperature | |
Dimensions L × W × H | 32 × 19 × 5 (mm) |
Weight | 10g |
Order number | 249020 |
Order name | Address Module/Conv. |
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • | |
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED |
|